Amnetz Series

On-Grid Inverter

MODEL

Amnetz 1.5K

GENERAL

Dimension 160 x 270 x 450mm (D x W x H)
Net Weight (kgs) 12.7

INPUT (DC)

Max. DC Power 1650 W
Maximum DC Voltage 500 VDC
MPP Voltage Range 125 VDC ~ 450 VDC
Nominal DC Voltage 370 VDC
Start-up Voltage / Initial Feeding Voltage 125VDC / 150VDC
Maximum Input Current 1 x 13A
Number of MPP Trackers / Strings per MPP Tracker 1 / A:1

OUTPUT

AC Nominal Power 1500 W
Maximum AC Apparent Power 1500 VA
Nominal AC Voltage 230 VAC
AC Voltage Range 184-264 VAC*
AC Grid Frequency 50 Hz / 60 Hz
Nominal Output Current 6.6 A
Power Factor @ Rated Power > 0.99

PROTECTION & EFFICIENCY

DC Reverse-Polarity Protection Yes
Ground Fault Monitoring Yes
Grid Monitoring Yes
AC Short Circuit Protection Yes
Over Current Protection 30 A
Maximum Efficiency 96%
Amnetz 2K

GENERAL

Dimension 160 x 270 x 450mm (D x W x H)
Net Weight (kgs) 12.7

INPUT (DC)

Max. DC Power 2200 W
Maximum DC Voltage 500 VDC
MPP Voltage Range 170 VDC ~ 450 VDC
Nominal DC Voltage 370 VDC
Start-up Voltage / Initial Feeding Voltage 125VDC / 150VDC
Maximum Input Current 1 x 13A
Number of MPP Trackers / Strings per MPP Tracker 1 / A:1

OUTPUT

AC Nominal Power 2000 W
Maximum AC Apparent Power 2000 VA
Nominal AC Voltage 230 VAC
AC Voltage Range 184-264 VAC*
AC Grid Frequency 50 Hz / 60 Hz
Nominal Output Current 8.7A
Power Factor @ Rated Power > 0.99

PROTECTION & EFFICIENCY

DC Reverse-Polarity Protection Yes
Ground Fault Monitoring Yes
Grid Monitoring Yes
AC Short Circuit Protection Yes
Over Current Protection 30 A
Maximum Efficiency 96%
Amnetz 3K

GENERAL

Dimension 160 x 270 x 450mm (D x W x H)
Net Weight (kgs) 12.7

INPUT (DC)

Max. DC Power 3300 W
Maximum DC Voltage 500 VDC
MPP Voltage Range 250 VDC ~ 500 VDC
Nominal DC Voltage 370 VDC
Start-up Voltage / Initial Feeding Voltage 125VDC / 150VDC
Maximum Input Current 1 x 13A
Number of MPP Trackers / Strings per MPP Tracker 1 / A:1

OUTPUT

AC Nominal Power 3000 W
Maximum AC Apparent Power 3000 VA
Nominal AC Voltage 230 VAC
AC Voltage Range 184-264 VAC*
AC Grid Frequency 50 Hz / 60 Hz
Nominal Output Current 13A
Power Factor @ Rated Power > 0.99

PROTECTION & EFFICIENCY

DC Reverse-Polarity Protection Yes
Ground Fault Monitoring Yes
Grid Monitoring Yes
AC Short Circuit Protection Yes
Over Current Protection 30 A
Maximum Efficiency 97.0%
Amnetz 5K

GENERAL

Dimension 182 x 308 x 515mm (D x W x H)
Net Weight (kgs) 20.5

INPUT (DC)

Max. DC Power 5000W
Maximum DC Voltage 500 VDC
MPP Voltage Range 180 VDC ~ 500 VDC
Nominal DC Voltage 370 VDC
Start-up Voltage / Initial Feeding Voltage 125VDC / 150VDC
Maximum Input Current 2 x 13A
Number of MPP Trackers / Strings per MPP Tracker 2 / A:1;B:1

OUTPUT

AC Nominal Power 4600 W (only apply for
VDE 4105) or 5000 W
Maximum AC Apparent Power 4600 VA (only apply for
VDE 4105) or 5000 VA
Nominal AC Voltage 230 VAC
AC Voltage Range 184-264 VAC*
AC Grid Frequency 50 Hz / 60 Hz
Nominal Output Current 20A
Power Factor @ Rated Power > 0.99

PROTECTION & EFFICIENCY

DC Reverse-Polarity Protection Yes
Ground Fault Monitoring Yes
Grid Monitoring Yes
AC Short Circuit Protection Yes
Over Current Protection 50 A
Maximum Efficiency 97.0%

DOWNLOAD

Document Date Version
2017-08-07 1.00
2017-08-07 1.00

You may also like…

Off-Grid Inverter

On-Grid Inverter

Hybrid  Inverter

Hybrid Inverter

Off-Grid Inverter