MODEL
PRO606-S/L 6KVA
GENERAL
UPS Type | Tower |
Phase | Single phase with ground |
Rating (VA) | 6000VA |
Nominal Power (W) | 4800W |
Standard Model Dimension (mm) | 562 x 300 x 830 (D x W x H) |
Weight (kg) | 106 |
Long-run Model Dimension (mm) | 562 x 250 x 830 (D x W x H) |
Weight (kg) | 62 |
INPUT
Connection Type | Terminal |
Nominal Voltage | 208VAC/220VAC/230 VAC |
Voltage Range | 165VAC ~ 275VAC @ 16 pcs of batteries 185VAC ~ 275VAC @ 18 pcs of batteries |
Frequency Range | 40 Hz ~ 55 Hz @ 50Hz system 56 Hz ~ 64 Hz @ 60Hz system |
OUTPUT
Connection Type | Terminal |
Output Voltage | 208VAC/220VAC/230 VAC |
Voltage Regulation | ±1% |
Frequency Range (Synchronized Range) | 45Hz ~ 55 Hz or 56 Hz ~ 64 Hz |
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Current Crest Ratio | 3:1 |
Harmonic Distortion | ≦3% THD (Linear load) ≦5% THD (Non-linear load) |
ALARM & INDICATORS
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continuously sounding |
LCD | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
CONNECTIVITY, CONTROL & MONITORING
Front panel | Status LED, Function keys, LCD display |
Communication | Smart RS232* USB Port Emergency Power Off (EPO) |
BATTERY
Standard Model Type | 12V / 9Ah |
Numbers | 16 |
Typical Recharge Time | 6 hours recover to 90% capacity |
Long-run Model Type | Depending on the capacity of external batteries |
Numbers | 16 / 18 |
Charging Current (max) | Default :8 A ± 10%; Max: 2A, 4A, 8A (Adjustable) |
REAR PANEL
|

PRO608-S/L 7.5KVA
GENERAL
UPS Type | Tower |
Phase | Single phase with ground |
Rating (VA) | 7500VA |
Nominal Power (W) | 6000W |
Standard Model Dimension (mm) | 562 x 300 x 830 (D x W x H) |
Weight (kg) | 122 |
Long-run Model Dimension (mm) | 562 x 250 x 830 (D x W x H) |
Weight (kg) | 78 |
INPUT
Connection Type | Terminal |
Nominal Voltage | 208VAC/220VAC/230 VAC |
Voltage Range | 165VAC ~ 275VAC @ 16 pcs of batteries 185VAC ~ 275VAC @ 18 pcs of batteries |
Frequency Range | 40 Hz ~ 55 Hz @ 50Hz system 56 Hz ~ 64 Hz @ 60Hz system |
OUTPUT
Connection Type | Terminal |
Output Voltage | 208VAC/220VAC/230 VAC |
Voltage Regulation | ±1% |
Frequency Range (Synchronized Range) | 45Hz ~ 55 Hz or 56 Hz ~ 64 Hz |
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Current Crest Ratio | 3:1 |
Harmonic Distortion | ≦3% THD (Linear load) ≦5% THD (Non-linear load) |
ALARM & INDICATORS
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continuously sounding |
LCD | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
CONNECTIVITY, CONTROL & MONITORING
Front panel | Status LED, Function keys, LCD display |
Communication | Smart RS232* USB Port Emergency Power Off (EPO) |
BATTERY
Standard Model Type | 12V / 9Ah |
Numbers | 16 |
Typical Recharge Time | 6 hours recover to 90% capacity |
Long-run Model Type | Depending on the capacity of external batteries |
Numbers | 16 / 18 |
Charging Current (max) | Default :8 A ± 10%; Max: 2A, 4A, 8A (Adjustable) |
REAR PANEL
|

PRO610-S/L 10KVA
GENERAL
UPS Type | Tower |
Phase | Single phase with ground |
Rating (VA) | 10000VA |
Nominal Power (W) | 8000W |
Standard Model Dimension (mm) | 562 x 300 x 830 (D x W x H) |
Weight (kg) | 130 |
Long-run Model Dimension (mm) | 562 x 250 x 830 (D x W x H) |
Weight (kg) | 86 |
INPUT
Connection Type | Terminal |
Nominal Voltage | 208VAC/220VAC/230 VAC |
Voltage Range | 165VAC ~ 275VAC @ 16 pcs of batteries 185VAC ~ 275VAC @ 18 pcs of batteries |
Frequency Range | 40 Hz ~ 55 Hz @ 50Hz system 56 Hz ~ 64 Hz @ 60Hz system |
OUTPUT
Connection Type | Terminal |
Output Voltage | 208VAC/220VAC/230 VAC |
Voltage Regulation | ±1% |
Frequency Range (Synchronized Range) | 45Hz ~ 55 Hz or 56 Hz ~ 64 Hz |
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Current Crest Ratio | 3:1 |
Harmonic Distortion | ≦3% THD (Linear load) ≦5% THD (Non-linear load) |
ALARM & INDICATORS
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continuously sounding |
LCD | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators |
CONNECTIVITY, CONTROL & MONITORING
Front panel | Status LED, Function keys, LCD display |
Communication | Smart RS232* USB Port Emergency Power Off (EPO) |
BATTERY
Standard Model Type | 12V / 9Ah |
Numbers | 16 |
Typical Recharge Time | 6 hours recover to 90% capacity |
Long-run Model Type | Depending on the capacity of external batteries |
Numbers | 16 / 18 |
Charging Current (max) | Default :8 A ± 10%; Max: 2A, 4A, 8A (Adjustable) |
REAR PANEL
|