Master II Series (1P/1P) – Rack/Tower

PRO800-QRS/QRL SERIES 1-10KVA

DSP technology guarantees high performance

True Double-Conversion

Output power factor 1

Wide input voltage range (110-300 VAC)

Active input power factor correction 0.99

50/60Hz Frequency Converter Mode

MODEL

PRO801-QRS 1KVA

GENERAL

UPS Type Rack / Tower
Phase Single phase with ground
Rating (VA) 1000
Nominal Power (W) 1000
Dimension (mm) 410 x 438 x 88 (D x W x H)
Weight (kg) 14.1 (with battery)

7.8 (without battery)

INPUT

Connection Type IEC 320-C14
Nominal Voltage 200/208/220/230/240 VAC
Voltage Range 110-300 VAC ± 5% @ 50% load

160-300 VAC ± 5% @ 100% load

Frequency Range 40Hz ~ 70Hz
Power Factor ≧0.99
Harmonic Distortion(THDi) ≦ 5% @ nominal input voltage

OUTPUT

Connection Type 8 x IEC 320-C13
Nominal Voltage 200*/208*/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 57 ~ 63 Hz or 47 ~ 53 Hz
Frequency Range (Batt. Mode) 60Hz ± 0.1Hz or 50 Hz ± 0.1Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦2% THD (Linear load)

≦4% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 5 seconds
Low Battery Sounding every 2 seconds
Overload Sounding every second
Fault Continuously sounding
LCD UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

Type 12V / 7Ah
Numbers 3
Typical Recharge Time  3 hours recover to 95% capacity for internal battery @2A charging current
Charging Current Default 2A, max 12A adjustable

REAR PANEL

  1. Programmable outlets: connect to non-critical loads
  2. Output receptacles: connect to mission-critical loads
  3. AC input
  4. Network/Fax/Modem surge protection
  5. USB communication port
  6. RS-232 communication port
  7. Intelligent slot
  8. Emergency power off function connector (EPO)
  9. External battery connection
  10. Cooling fan
PRO8015-QRS 1.5KVA

GENERAL

UPS Type Rack / Tower
Phase Single phase with ground
Rating (VA) 1500
Nominal Power (W) 1500
Dimension (mm) 410 x 438 x 88 (D x W x H)
Weight (kg) 15.5 (with battery)

8.1 (without battery)

INPUT

Connection Type IEC 320-C14
Nominal Voltage 200/208/220/230/240 VAC
Voltage Range 110-300 VAC ± 5% @ 50% load

160-300 VAC ± 5% @ 100% load

Frequency Range 40Hz ~ 70Hz
Power Factor ≧0.99
Harmonic Distortion(THDi) ≦ 5% @ nominal input voltage

OUTPUT

Connection Type 8 x IEC 320-C13
Nominal Voltage 200*/208*/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 57 ~ 63 Hz or 47 ~ 53 Hz
Frequency Range (Batt. Mode) 60Hz ± 0.1Hz or 50 Hz ± 0.1Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦2% THD (Linear load)

≦4% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 5 seconds
Low Battery Sounding every 2 seconds
Overload Sounding every second
Fault Continuously sounding
LCD UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

Type 12V / 9Ah
Numbers 3
Typical Recharge Time  3 hours recover to 95% capacity for internal battery @2A charging current
Charging Current Default 2A, max 12A adjustable

REAR PANEL

  1. Programmable outlets: connect to non-critical loads
  2. Output receptacles: connect to mission-critical loads
  3. AC input
  4. Network/Fax/Modem surge protection
  5. USB communication port
  6. RS-232 communication port
  7. Intelligent slot
  8. Emergency power off function connector (EPO)
  9. External battery connection
  10. Cooling fan
PRO802-QRS 2KVA

GENERAL

UPS Type Rack / Tower
Phase Single phase with ground
Rating (VA) 2000
Nominal Power (W) 2000
Dimension (mm) 630 x 438 x 88 (D x W x H)
Weight (kg) 10.6 (without battery)

23.3 (w/built-int battery)

INPUT

Connection Type IEC 320-C20
Nominal Voltage 200/208/220/230/240 VAC
Voltage Range 110-300 VAC ± 5% @ 50% load

160-300 VAC ± 5% @ 100% load

Frequency Range 40Hz ~ 70Hz
Power Factor ≧0.99
Harmonic Distortion(THDi) ≦ 5% @ nominal input voltage

OUTPUT

Connection Type 8 x IEC 320-C13
Nominal Voltage 200*/208*/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 57 ~ 63 Hz or 47 ~ 53 Hz
Frequency Range (Batt. Mode) 60Hz ± 0.1Hz or 50 Hz ± 0.1Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦2% THD (Linear load)

≦4% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 5 seconds
Low Battery Sounding every 2 seconds
Overload Sounding every second
Fault Continuously sounding
LCD UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

Type 12V / 7Ah
Numbers 6
Typical Recharge Time  3 hours recover to 95% capacity for internal battery @2A charging current
Charging Current Default 2A, max 8A adjustable

REAR PANEL

  1. Programmable outlets: connect to non-critical loads
  2. Output receptacles: connect to mission-critical loads
  3. AC input
  4. Network/Fax/Modem surge protection
  5. USB communication port
  6. RS-232 communication port
  7. Intelligent slot
  8. Emergency power off function connector (EPO)
  9. External battery connection
  10. Cooling fan
PRO803-QRS 3KVA

GENERAL

UPS Type Rack / Tower
Phase Single phase with ground
Rating (VA) 3000
Nominal Power (W) 3000
Dimension (mm) 630 x 438 x 88 (D x W x H)
Weight (kg) 27.5 (with battery)

12.4 (without battery)

INPUT

Connection Type IEC 320-C20
Nominal Voltage 200/208/220/230/240 VAC
Voltage Range 110-300 VAC ± 5% @ 50% load

160-300 VAC ± 5% @ 100% load

Frequency Range 40Hz ~ 70Hz
Power Factor ≧0.99
Harmonic Distortion(THDi) ≦ 5% @ nominal input voltage

OUTPUT

Connection Type 8 x IEC 320-C13

1 x IEC 320-C19

Nominal Voltage 200*/208*/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 57 ~ 63 Hz or 47 ~ 53 Hz
Frequency Range (Batt. Mode) 60Hz ± 0.1Hz or 50 Hz ± 0.1Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦2% THD (Linear load)

≦4% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 5 seconds
Low Battery Sounding every 2 seconds
Overload Sounding every second
Fault Continuously sounding
LCD UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

Type 12V / 9Ah
Numbers 6
Typical Recharge Time  3 hours recover to 95% capacity for internal battery @2A charging current
Charging Current Default 2A, max 8A adjustable

REAR PANEL

  1. Programmable outlets: connect to non-critical loads
  2. Output receptacles: connect to mission-critical loads
  3. AC input
  4. Network/Fax/Modem surge protection
  5. USB communication port
  6. RS-232 communication port
  7. Intelligent slot
  8. Emergency power off function connector (EPO)
  9. External battery connection
  10. Cooling fan
PRO806-QRS/QRL 6KVA

GENERAL

UPS Type Rack / Tower
Phase 1 phase in / 1 phase out
Rating (VA) 6000
Nominal Power (W) 6000
Standard Model

Dimension (mm)

UPS Unit: 610 x 438 x 88 [2U] (D x W x H)

Battery Pack: 600 x 438 x 133 [3U] (D x W x H)

Weight (kg) UPS Unit: 17

Battery Pack: 57

Long-run Model

Dimension (mm)

610 x 438 x 88 [2U] (D x W x H)
Weight (kg) 17

INPUT

Connection Type Terminal
Nominal Voltage 208/220/230/240 VAC VAC
Voltage Range 110~300VAC ± 3% at 50% load

176~300VAC ± 3% at 100% load

Frequency Range 46~54 Hz ◎ 50Hz / 56~64 Hz ◎ 60Hz
Power Factor ≧0.99
THDi < 4% @100% Load

< 6% @50% Load

OUTPUT

Connection Type Terminal
Nominal Voltage 208*/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46~54 Hz ◎ 50Hz / 56~64 Hz ◎ 60Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦1% THD (Linear load)

≦4% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
LCD Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

Standard Model

Type

12V / 7Ah
Numbers 20
Typical Recharge Time  9 hours recover to 90% capacity
Long-run Model

Type

Depending on applications
Numbers 16 - 20 **
Charging Current (max) 4.0 A

REAR PANEL

  1. Share current port (only available for parallel model)
  2. Parallel port (only available for parallel model)
  3. External battery connector
  4. Intelligent slot
  5. RS-232 communication port
  6. USB communication port
  7. Emergency power off function connector (EPO connector)
  8. Input circuit breaker
  9. Output terminals
  10. Ground
  11. Input terminals
  12. Cooling Fan
  13. External maintenance bypass switch port

PRO810-QRS/QRL 10KVA

GENERAL

UPS Type Rack / Tower
Phase 1 phase in / 1 phase out
Rating (VA) 10000
Nominal Power (W) 10000
Standard Model

Dimension (mm)

UPS Unit: 610 x 438 x 88 [2U] (D x W x H)

Battery Pack: 600 x 438 x 133 [3U] (D x W x H)

Weight (kg) UPS Unit: 20

Battery Pack: 63

Long-run Model

Dimension (mm)

610 x 438 x 88 [2U] (D x W x H)
Weight (kg) 20

INPUT

Connection Type Terminal
Nominal Voltage 208/220/230/240 VAC VAC
Voltage Range 110~300VAC ± 3% at 50% load

176~300VAC ± 3% at 100% load

Frequency Range 46~54 Hz ◎ 50Hz / 56~64 Hz ◎ 60Hz
Power Factor ≧0.99
THDi < 4% @100% Load

< 6% @50% Load

OUTPUT

Connection Type Terminal
Nominal Voltage 208*/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46~54 Hz ◎ 50Hz / 56~64 Hz ◎ 60Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦1% THD (Linear load)

≦4% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
LCD Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

Standard Model

Type

12V / 9Ah
Numbers 20
Typical Recharge Time  9 hours recover to 90% capacity
Long-run Model

Type

Depending on the capacity of external batteries
Numbers 16 - 20 **
Charging Current (max) 4.0 A

REAR PANEL

  1. Share current port (only available for parallel model)
  2. Parallel port (only available for parallel model)
  3. External battery connector
  4. Intelligent slot
  5. RS-232 communication port
  6. USB communication port
  7. Emergency power off function connector (EPO connector)
  8. Input circuit breaker
  9. Output terminals
  10. Ground
  11. Input terminals