MODEL
GENERAL
UPS Type | Rack / Tower |
Phase | Single phase with ground |
Rating (VA) | 1000 |
Nominal Power (W) | 1000 |
Dimension (mm) | 410 x 438 x 88 (D x W x H) |
Weight (kg) | 14.1 (with battery)
7.8 (without battery) |
INPUT
Connection Type | IEC 320-C14 |
Nominal Voltage | 200/208/220/230/240 VAC |
Voltage Range | 110-300 VAC ± 5% @ 50% load
160-300 VAC ± 5% @ 100% load |
Frequency Range | 40Hz ~ 70Hz |
Power Factor | ≧0.99 |
Harmonic Distortion(THDi) | ≦ 5% @ nominal input voltage |
OUTPUT
Connection Type | 8 x IEC 320-C13 |
Nominal Voltage | 200*/208*/220/230/240 VAC |
Voltage Regulation | ±1% |
Frequency Range (Synchronized Range) | 57 ~ 63 Hz or 47 ~ 53 Hz |
Frequency Range (Batt. Mode) | 60Hz ± 0.1Hz or 50 Hz ± 0.1Hz |
Current Crest Ratio | 3:1 (max.) |
Harmonic Distortion | ≦2% THD (Linear load)
≦4% THD (Non-linear load) |
ALARM & INDICATORS
Battery Mode | Sounding every 5 seconds |
Low Battery | Sounding every 2 seconds |
Overload | Sounding every second |
Fault | Continuously sounding |
LCD | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
CONNECTIVITY, CONTROL & MONITORING
Front panel | Status LED, Function keys, LCD display |
Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
Type | 12V / 7Ah |
Numbers | 3 |
Typical Recharge Time | 3 hours recover to 95% capacity for internal battery @2A charging current |
Charging Current | Default 2A, max 12A adjustable |
REAR PANEL
|

GENERAL
UPS Type | Rack / Tower |
Phase | Single phase with ground |
Rating (VA) | 1500 |
Nominal Power (W) | 1500 |
Dimension (mm) | 410 x 438 x 88 (D x W x H) |
Weight (kg) | 15.5 (with battery)
8.1 (without battery) |
INPUT
Connection Type | IEC 320-C14 |
Nominal Voltage | 200/208/220/230/240 VAC |
Voltage Range | 110-300 VAC ± 5% @ 50% load
160-300 VAC ± 5% @ 100% load |
Frequency Range | 40Hz ~ 70Hz |
Power Factor | ≧0.99 |
Harmonic Distortion(THDi) | ≦ 5% @ nominal input voltage |
OUTPUT
Connection Type | 8 x IEC 320-C13 |
Nominal Voltage | 200*/208*/220/230/240 VAC |
Voltage Regulation | ±1% |
Frequency Range (Synchronized Range) | 57 ~ 63 Hz or 47 ~ 53 Hz |
Frequency Range (Batt. Mode) | 60Hz ± 0.1Hz or 50 Hz ± 0.1Hz |
Current Crest Ratio | 3:1 (max.) |
Harmonic Distortion | ≦2% THD (Linear load)
≦4% THD (Non-linear load) |
ALARM & INDICATORS
Battery Mode | Sounding every 5 seconds |
Low Battery | Sounding every 2 seconds |
Overload | Sounding every second |
Fault | Continuously sounding |
LCD | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
CONNECTIVITY, CONTROL & MONITORING
Front panel | Status LED, Function keys, LCD display |
Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
Type | 12V / 9Ah |
Numbers | 3 |
Typical Recharge Time | 3 hours recover to 95% capacity for internal battery @2A charging current |
Charging Current | Default 2A, max 12A adjustable |
REAR PANEL
|

GENERAL
UPS Type | Rack / Tower |
Phase | Single phase with ground |
Rating (VA) | 2000 |
Nominal Power (W) | 2000 |
Dimension (mm) | 630 x 438 x 88 (D x W x H) |
Weight (kg) | 10.6 (without battery)
23.3 (w/built-int battery) |
INPUT
Connection Type | IEC 320-C20 |
Nominal Voltage | 200/208/220/230/240 VAC |
Voltage Range | 110-300 VAC ± 5% @ 50% load
160-300 VAC ± 5% @ 100% load |
Frequency Range | 40Hz ~ 70Hz |
Power Factor | ≧0.99 |
Harmonic Distortion(THDi) | ≦ 5% @ nominal input voltage |
OUTPUT
Connection Type | 8 x IEC 320-C13 |
Nominal Voltage | 200*/208*/220/230/240 VAC |
Voltage Regulation | ±1% |
Frequency Range (Synchronized Range) | 57 ~ 63 Hz or 47 ~ 53 Hz |
Frequency Range (Batt. Mode) | 60Hz ± 0.1Hz or 50 Hz ± 0.1Hz |
Current Crest Ratio | 3:1 (max.) |
Harmonic Distortion | ≦2% THD (Linear load)
≦4% THD (Non-linear load) |
ALARM & INDICATORS
Battery Mode | Sounding every 5 seconds |
Low Battery | Sounding every 2 seconds |
Overload | Sounding every second |
Fault | Continuously sounding |
LCD | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
CONNECTIVITY, CONTROL & MONITORING
Front panel | Status LED, Function keys, LCD display |
Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
Type | 12V / 7Ah |
Numbers | 6 |
Typical Recharge Time | 3 hours recover to 95% capacity for internal battery @2A charging current |
Charging Current | Default 2A, max 8A adjustable |
REAR PANEL
|

GENERAL
UPS Type | Rack / Tower |
Phase | Single phase with ground |
Rating (VA) | 3000 |
Nominal Power (W) | 3000 |
Dimension (mm) | 630 x 438 x 88 (D x W x H) |
Weight (kg) | 27.5 (with battery)
12.4 (without battery) |
INPUT
Connection Type | IEC 320-C20 |
Nominal Voltage | 200/208/220/230/240 VAC |
Voltage Range | 110-300 VAC ± 5% @ 50% load
160-300 VAC ± 5% @ 100% load |
Frequency Range | 40Hz ~ 70Hz |
Power Factor | ≧0.99 |
Harmonic Distortion(THDi) | ≦ 5% @ nominal input voltage |
OUTPUT
Connection Type | 8 x IEC 320-C13
1 x IEC 320-C19 |
Nominal Voltage | 200*/208*/220/230/240 VAC |
Voltage Regulation | ±1% |
Frequency Range (Synchronized Range) | 57 ~ 63 Hz or 47 ~ 53 Hz |
Frequency Range (Batt. Mode) | 60Hz ± 0.1Hz or 50 Hz ± 0.1Hz |
Current Crest Ratio | 3:1 (max.) |
Harmonic Distortion | ≦2% THD (Linear load)
≦4% THD (Non-linear load) |
ALARM & INDICATORS
Battery Mode | Sounding every 5 seconds |
Low Battery | Sounding every 2 seconds |
Overload | Sounding every second |
Fault | Continuously sounding |
LCD | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
CONNECTIVITY, CONTROL & MONITORING
Front panel | Status LED, Function keys, LCD display |
Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
Type | 12V / 9Ah |
Numbers | 6 |
Typical Recharge Time | 3 hours recover to 95% capacity for internal battery @2A charging current |
Charging Current | Default 2A, max 8A adjustable |
REAR PANEL
|

GENERAL
UPS Type | Rack / Tower |
Phase | 1 phase in / 1 phase out |
Rating (VA) | 6000 |
Nominal Power (W) | 6000 |
Standard Model
Dimension (mm) |
UPS Unit: 610 x 438 x 88 [2U] (D x W x H)
Battery Pack: 600 x 438 x 133 [3U] (D x W x H) |
Weight (kg) | UPS Unit: 17
Battery Pack: 57 |
Long-run Model
Dimension (mm) |
610 x 438 x 88 [2U] (D x W x H) |
Weight (kg) | 17 |
INPUT
Connection Type | Terminal |
Nominal Voltage | 208/220/230/240 VAC VAC |
Voltage Range | 110~300VAC ± 3% at 50% load
176~300VAC ± 3% at 100% load |
Frequency Range | 46~54 Hz ◎ 50Hz / 56~64 Hz ◎ 60Hz |
Power Factor | ≧0.99 |
THDi | < 4% @100% Load
< 6% @50% Load |
OUTPUT
Connection Type | Terminal |
Nominal Voltage | 208*/220/230/240 VAC |
Voltage Regulation | ±1% |
Frequency Range (Synchronized Range) | 46~54 Hz ◎ 50Hz / 56~64 Hz ◎ 60Hz |
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Current Crest Ratio | 3:1 (max.) |
Harmonic Distortion | ≦1% THD (Linear load)
≦4% THD (Non-linear load) |
ALARM & INDICATORS
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continuously sounding |
LCD | Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault |
CONNECTIVITY, CONTROL & MONITORING
Front panel | Status LED, Function keys, LCD display |
Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
Standard Model
Type |
12V / 7Ah |
Numbers | 20 |
Typical Recharge Time | 9 hours recover to 90% capacity |
Long-run Model
Type |
Depending on applications |
Numbers | 16 - 20 ** |
Charging Current (max) | 4.0 A |
REAR PANEL
|

GENERAL
UPS Type | Rack / Tower |
Phase | 1 phase in / 1 phase out |
Rating (VA) | 10000 |
Nominal Power (W) | 10000 |
Standard Model
Dimension (mm) |
UPS Unit: 610 x 438 x 88 [2U] (D x W x H)
Battery Pack: 600 x 438 x 133 [3U] (D x W x H) |
Weight (kg) | UPS Unit: 20
Battery Pack: 63 |
Long-run Model
Dimension (mm) |
610 x 438 x 88 [2U] (D x W x H) |
Weight (kg) | 20 |
INPUT
Connection Type | Terminal |
Nominal Voltage | 208/220/230/240 VAC VAC |
Voltage Range | 110~300VAC ± 3% at 50% load
176~300VAC ± 3% at 100% load |
Frequency Range | 46~54 Hz ◎ 50Hz / 56~64 Hz ◎ 60Hz |
Power Factor | ≧0.99 |
THDi | < 4% @100% Load
< 6% @50% Load |
OUTPUT
Connection Type | Terminal |
Nominal Voltage | 208*/220/230/240 VAC |
Voltage Regulation | ±1% |
Frequency Range (Synchronized Range) | 46~54 Hz ◎ 50Hz / 56~64 Hz ◎ 60Hz |
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz |
Current Crest Ratio | 3:1 (max.) |
Harmonic Distortion | ≦1% THD (Linear load)
≦4% THD (Non-linear load) |
ALARM & INDICATORS
Battery Mode | Sounding every 4 seconds |
Low Battery | Sounding every second |
Overload | Sounding twice every second |
Fault | Continuously sounding |
LCD | Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault |
CONNECTIVITY, CONTROL & MONITORING
Front panel | Status LED, Function keys, LCD display |
Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
Standard Model
Type |
12V / 9Ah |
Numbers | 20 |
Typical Recharge Time | 9 hours recover to 90% capacity |
Long-run Model
Type |
Depending on the capacity of external batteries |
Numbers | 16 - 20 ** |
Charging Current (max) | 4.0 A |
REAR PANEL
|