Master II Series (1P/1P)

PRO800-QS/QL SERIES 1-10KVA

Microprocessor control optimizes reliability*

True Double-Conversion

Output power factor 1

Emergency power off function (EPO)

Active input power factor correction 0.99^

Provides over voltage cut-off protection and
surge immunity by MOV for full time
equipment protection*

*Only available for 1-3KVA models | ^Only available for 6-10KVA models

MODEL

PRO801-QS 1KVA

GENERAL

UPS Type Tower
Phase Single phase with ground
Rating (VA) 1000
Nominal Power (W) 1000
Dimension (mm) 397 x 145 x 220 (D x W x H)
Weight (kg) 13 (with battery)

6.6 (without battery)

INPUT

Connection Type IEC 320-C14
Nominal Voltage 200/208/220/230/240 VAC
Voltage Range 110-300 VAC (Based on load at 50%)

160-300 VAC (Based on load at 100%)

Frequency Range 40 Hz ~ 70 Hz
Power Factor ≧0.99
THDi ≦ 5%

OUTPUT

Connection Type 4 x IEC 320-C13
Nominal Voltage 200*/208*/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 47~53 Hz or 57~63 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≦2% THD (Linear load)

≦4% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 5 seconds
Low Battery Sounding every 2 seconds
Overload Sounding every second
Fault Continuously sounding
LCD Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

Type 12V / 7Ah
Numbers 3
Typical Recharge Time  3 hours recover to 95% capacity for internal battery @2A charging current
Charging Current Default 2A, max 12A adjustable

REAR PANEL

  1. Programmable outlets: connect to non-critical loads
  2. Output receptacles: connect to mission-critical loads
  3. AC input
  4. Network/Fax/Modem surge protection
  5. USB communication port
  6. RS-232 communication port
  7. Intelligent slot
  8. Emergency power off function connector (EPO)
  9. External battery connection
  10. Cooling fan
PRO8015-QS 1.5KVA

GENERAL

UPS Type Tower
Phase Single phase with ground
Rating (VA) 1500
Nominal Power (W) 1500
Dimension (mm) 397 x 145 x 220 (D x W x H)
Weight (kg) 14.6 (with battery)

7 (without battery)

INPUT

Connection Type IEC 320-C14
Nominal Voltage 200/208/220/230/240 VAC
Voltage Range 110-300 VAC (Based on load at 50%)

160-300 VAC (Based on load at 100%)

Frequency Range 40 Hz ~ 70 Hz
Power Factor ≧0.99
THDi ≦ 5%

OUTPUT

Connection Type 4 x IEC 320-C13
Nominal Voltage 200*/208*/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 47~53 Hz or 57~63 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≦2% THD (Linear load)

≦4% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 5 seconds
Low Battery Sounding every 2 seconds
Overload Sounding every second
Fault Continuously sounding
LCD Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys. LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

Type 12 V / 9 AH
Numbers 3
Typical Recharge Time  3 hours recover to 95% capacity for internal battery @2A charging current
Charging Current Default 2A, max 12A adjustable

REAR PANEL

  1. Programmable outlets: connect to non-critical loads
  2. Output receptacles: connect to mission-critical loads
  3. AC input
  4. Network/Fax/Modem surge protection
  5. USB communication port
  6. RS-232 communication port
  7. Intelligent slot
  8. Emergency power off function connector (EPO)
  9. External battery connection
  10. Cooling fan
PRO802-QS 2KVA

GENERAL

UPS Type Tower
Phase Single phase with ground
Rating (VA) 2000
Nominal Power (W) 2000
Dimension (mm) 421 x 190 x 318 (D x W x H)
Weight (kg) 23.2 (with battery)

9.9 (without battery)

INPUT

Connection Type IEC 320-C20
Nominal Voltage 200/208/220/230/240 VAC
Voltage Range 110-300 VAC (Based on load at 50%)

160-300 VAC (Based on load at 100%)

Frequency Range 40 Hz ~ 70 Hz
Power Factor ≧0.99
THDi ≦ 5%

OUTPUT

Connection Type 8 x IEC 320-C13
Nominal Voltage 200*/208*/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 47~53 Hz or 57~63 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≦2% THD (Linear load)

≦4% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 5 seconds
Low Battery Sounding every 2 seconds
Overload Sounding every second
Fault Continuously sounding
LCD Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

Type 12 V / 7 AH
Numbers 6
Typical Recharge Time  3 hours recover to 95% capacity for internal battery @2A charging current
Charging Current Default 2A, max 8A adjustable

REAR PANEL

  1. Programmable outlets: connect to non-critical loads
  2. Output receptacles: connect to mission-critical loads
  3. AC input
  4. Network/Fax/Modem surge protection
  5. USB communication port
  6. RS-232 communication port
  7. Intelligent slot
  8. Emergency power off function connector (EPO)
  9. External battery connection
  10. Cooling fan
PRO803-QS 3KVA

GENERAL

UPS Type Tower
Phase Single phase with ground
Rating (VA) 3000
Nominal Power (W) 3000
Dimension (mm) 421 x 190 x 318 (D x W x H)
Weight (kg) 28 (with battery)

12.3 (without battery)

INPUT

Connection Type IEC 320-C20
Nominal Voltage 200/208/220/230/240 VAC
Voltage Range 110-300 VAC (Based on load at 50%)

160-300 VAC (Based on load at 100%)

Frequency Range 40 Hz ~ 70 Hz
Power Factor ≧0.99
THDi ≦ 5%

OUTPUT

Connection Type 8 x IEC 320-C13

1 x IEC 320-C19

Nominal Voltage 200*/208*/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 47~53 Hz or 57~63 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≦2% THD (Linear load)

≦4% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 5 seconds
Low Battery Sounding every 2 seconds
Overload Sounding every second
Fault Continuously sounding
LCD Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

Type 12 V / 9 AH
Numbers 6
Typical Recharge Time  3 hours recover to 95% capacity for internal battery @2A charging current
Charging Current Default 2A, max 8A adjustable

REAR PANEL

  1. Programmable outlets: connect to non-critical loads
  2. Output receptacles: connect to mission-critical loads
  3. AC input
  4. Network/Fax/Modem surge protection
  5. USB communication port
  6. RS-232 communication port
  7. Intelligent slot
  8. Emergency power off function connector (EPO)
  9. External battery connection
  10. Cooling fan
PRO806-QS/QL 6KVA

GENERAL

UPS Type Tower
Phase 1 phase in / 1 phase out
Rating (VA) 6000
Nominal Power (W) 6000
Standard Model

Dimension (mm)

592 x 250 x 576 (D x W x H)
Weight (kg) 81
Long-run Model

Dimension (mm)

592 x 250 x 576 (D x W x H)
Weight (kg) 25

INPUT

Connection Type Terminal
Nominal Voltage 208/220/230/240 VAC
Voltage Range 110-300VAC ± 3% at 50% load

176~300VAC ± 3% at 100% load

Frequency Range 46~54 Hz or 56~64 Hz
Power Factor ≧0.99
THDi <4% @100% Load

<6% @50% Loadd

OUTPUT

Connection Type Terminal

2 x IEC 320-C13

Nominal Voltage 208/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46~54 Hz or 56~64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≦1% THD (Linear load)

≦4% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 4 seconds
Low Battery Sounding every 2 seconds
Overload Sounding twice every second
Fault Continuously sounding
LCD Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

Standard Model

Type

12V / 7Ah
Numbers 20
Typical Recharge Time  9 hours recover to 90% capacity
Long-run Model

Type

Depending on the capacity of external batteries
Numbers 16 - 20 **
Charging Current (max) 4.0 A (Parallelable up to 3 charger boards to reach 12A maximum)

REAR PANEL

  1. RS-232 communication port
  2. USB communication port
  3. Emergency power off function connector (EPO)
  4. Share current port (only available for parallel model)
  5. Parallel port (only available for parallel model
  6. Intelligent slot
  7. Cooling fan
  8. Maintenance bypass switch
  9. Input circuit breaker
  10. Output receptacles: connect to mission-critical loads
  11. Output circuit breaker for receptacles
  12. Output terminal: connect to mission-critical loads
  13. External battery connector
  14. Utility input terminal
PRO806-QL 6KVA(18Ah)

GENERAL

UPS Type Tower
Phase 1 phase in / 1 phase out
Rating (VA) 6000
Nominal Power (W) 6000
Long-run Model

Dimension (mm)

592 x 250 x 576 (D x W x H)
Weight (kg) 25

INPUT

Connection Type Terminal
Nominal Voltage 208/220/230/240 VAC
Voltage Range 110-300VAC ± 3% at 50% load

176~300VAC ± 3% at 100% load

Frequency Range 46~54 Hz or 56~64 Hz
Power Factor ≧0.99
THDi <4% @100% Load

<6% @50% Loadd

OUTPUT

Connection Type Terminal

2 x IEC 320-C13

Nominal Voltage 208/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46~54 Hz or 56~64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≦1% THD (Linear load)

≦4% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 4 seconds
Low Battery Sounding every 2 seconds
Overload Sounding twice every second
Fault Continuously sounding
LCD Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

Long-run Model

Type

18Ah (with X4 battery cabinet)
Numbers 20
Charging Current (max) 4.0 A (Parallelable up to 3 charger boards to reach 12A maximum)

REAR PANEL

  1. RS-232 communication port
  2. USB communication port
  3. Emergency power off function connector (EPO)
  4. Share current port (only available for parallel model)
  5. Parallel port (only available for parallel model
  6. Intelligent slot
  7. Cooling fan
  8. Maintenance bypass switch
  9. Input circuit breaker
  10. Output receptacles: connect to mission-critical loads
  11. Output circuit breaker for receptacles
  12. Output terminal: connect to mission-critical loads
  13. External battery connector
  14. Utility input terminal
PRO810-QS/QL 10KVA

GENERAL

UPS Type Tower
Phase 1 phase in / 1 phase out
Rating (VA) 10000
Nominal Power (W) 10000
Standard Model

Dimension (mm)

592 x 250 x 576 (D x W x H)
Weight (kg) 83
Long-run Model

Dimension (mm)

592 x 250 x 576 (D x W x H)
Weight (kg) 27

INPUT

Connection Type Terminal
Nominal Voltage 208/220/230/240 VAC
Voltage Range 110-300VAC ± 3% at 50% load

176~300VAC ± 3% at 100% load

Frequency Range 46~54 Hz or 56~64 Hz
Power Factor ≧0.99
THDi <4% @100% Load

<6% @50% Loadd

OUTPUT

Connection Type Terminal

2 x IEC 320-C13

Nominal Voltage 208/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46~54 Hz or 56~64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≦1% THD (Linear load)

≦4% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 4 seconds
Low Battery Sounding every 2 seconds
Overload Sounding twice every second
Fault Continuously sounding
LCD Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

Standard Model

Type

12V / 9Ah
Numbers 20
Typical Recharge Time  9 hours recover to 90% capacity
Long-run Model

Type

Depending on the capacity of external batteries
Numbers 16 - 20 **
Charging Current (max) 4.0 A (Parallelable up to 3 charger boards to reach 12A maximum)

REAR PANEL

  1. RS-232 communication port
  2. USB communication port
  3. Emergency power off function connector (EPO)
  4. Share current port (only available for parallel model)
  5. Parallel port (only available for parallel model
  6. Intelligent slot
  7. Cooling fan
  8. Maintenance bypass switch
  9. Input circuit breaker
  10. Output receptacles: connect to mission-critical loads
  11. Output circuit breaker for receptacles
  12. Output terminal: connect to mission-critical loads
  13. External battery connector
  14. Utility input terminal

DOWNLOAD

Document Date Version
2017-08-07 1.00
2017-08-07 1.00

You may also like…

PRO800-ES/EL SERIES 1-3KVA

PRO800-ERS/ERL SERIES 1-3KVA

PRO83300-FS/FL SERIES 30-200KVA

PRO83300-ERS/ERL SERIES 10-20KVA

PRO83100-ES/EL SERIES 10-30KVA