MODEL

PRO83310-QRS/QRL 10KVA

GENERAL

UPS Type Rack / Tower
Phase 3 phase in / 3 phase out
Rating (VA) 10000VA
Nominal Power (W) 10000W
Standard Model

Dimension (D x W x H) (mm)

UPS unit : 680 x 438 x 133 (3U)

Battery Pack : 580 x 438 x 133 (3U)

Weight (kg)

UPS unit : 34

Battery Pack : 63

Long-run Model

Dimension (D x W x H) (mm)

680 x 438 x 133 (3U)
Weight (kg) 34

INPUT

Connection Type Terminal
Nominal Voltage 3x 400VAC (3Ph+N)
Voltage Range 190-520 VAC (3-phase) at 50% load

305-478 VAC (3-phase) at 100% load

Frequency Range 46~54 Hz or 56~64Hz
Power Factor ≧0.99 @ 100% Load

OUTPUT

Connection Type Terminal
Nominal Voltage 3x 360/380/400/415 VAC (3Ph+N)
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46~54Hz or 56~64Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦2% THD (Linear load)

≦5% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
LCD UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

Standard Model

Type

12V / 9Ah
Numbers 20pcs (10+10)
Charging Current (max) 1A/2A/3A/4A/5A/6A/7A/8A/9A/10A/11A/12A (Adjustable)
12A maximum
Charging Voltage +/-136.5VDC
Long-run Model

Type

Depending on the capacity of external batteries
Numbers 20pcs (10+10)
Charging Current (max) 1A/2A/3A/4A/5A/6A/7A/8A/9A/10A/11A/12A (Adjustable)
12A maximum
Charging Voltage +/-13.65V*N (N = 10)

REAR PANEL

  1. Power switch
  2. External maintenance bypass switch port
  3. USB communication port
  4. Emergency power off function connector (EPO connector)
  5. Share current port (Optional for parallel model)
  6. Parallel port (Optional for parallel model)
  7. Intelligent slot
  8. External battery connector
  9. Input/ Output / Bypass Terminals
  10. Input grounding terminal
  11. Output grounding terminal
PRO83320-QRS/QRL 20KVA

GENERAL

UPS Type Rack / Tower
Phase 3 phase in / 3 phase out
Rating (VA) 20000VA
Nominal Power (W) 20000W
Standard Model

Dimension (D x W x H) (mm)

UPS unit : 680 x 438 x 133 (3U)

Battery Pack : 580 x 438 x 133 (3U) x 2pcs

Weight (kg)

UPS unit : 35

Battery Pack : 63 x 2pcs

Long-run Model

Dimension (D x W x H) (mm)

680 x 438 x 133 (3U)
Weight (kg) 35

INPUT

Connection Type Terminal
Nominal Voltage 3x 400VAC (3Ph+N)
Voltage Range 190-520 VAC (3-phase) at 50% load

305-478 VAC (3-phase) at 100% load

Frequency Range 46~54 Hz or 56~64Hz
Power Factor ≧0.99 @ 100% Load

OUTPUT

Connection Type Terminal
Nominal Voltage 3x 360/380/400/415 VAC (3Ph+N)
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46~54Hz or 56~64Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦2% THD (Linear load)

≦5% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
LCD UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

Standard Model

Type

12V / 9Ah
Numbers 40pcs (20+20)
Charging Current (max) 1A/2A/3A/4A/5A/6A/7A/8A/9A/10A/11A/12A (Adjustable)
12A maximum
Charging Voltage +/-273VDC
Long-run Model

Type

Depending on the capacity of external batteries
Numbers 32-40pcs (Adjustable)
Charging Current (max) 1A/2A/3A/4A/5A/6A/7A/8A/9A/10A/11A/12A (Adjustable)
12A maximum
Charging Voltage +/-13.65V*N (N = 16~20)

REAR PANEL

  1. Power switch
  2. External maintenance bypass switch port
  3. USB communication port
  4. Emergency power off function connector (EPO connector)
  5. Share current port (Optional for parallel model)
  6. Parallel port (Optional for parallel model)
  7. Intelligent slot
  8. External battery connector
  9. Input/ Output / Bypass Terminals
  10. Input grounding terminal
  11. Output grounding terminal

DOWNLOAD

Document Date Version
2017-08-07 1.00
PRO83310QRS/QRL
2020-07-22 1.00
PRO83320QRS/QRL
2020-07-22 1.00

You may also like…

PRO800-ES/EL SERIES 1-3KVA

PRO800-QS/QL SERIES 1-10KVA

PRO800-ERS/ERL SERIES 1-3KVA

PRO83100-ERS/ERL SERIES 10-20KVA