Master II Series (3P/3P)

PRO83300-FS/FL SERIES 30-200KVA

True double-conversion

DSP technology guarantees high performance

Output power factor 0.9

Active power factor correction in all phases

50/60Hz Frequency Converter Mode

ECO mode operation for energy saving

MODEL

PRO83310-FS/FL 10KVA

GENERAL

UPS Type Tower
Phase 3-phase in / 3-phase out
Standard Model

Dimension (mm)

630 x 250x 750 (D x W x H)
Weight (kg) 139
Long-run Model

Dimension (mm)

630 x 250 x 750 (D x W x H)
Weight (kg) 43

INPUT

Nominal Voltage 3 x 400 VAC (3Ph+N)
Voltage Range 190-520 VAC (3-phase) @ 50% load

305-478 VAC (3-phase) @ 100% load

Frequency Range 46~54 Hz or 56~64Hz
Power Factor ≧0.99 @ 100% Load

OUTPUT

Output Voltage 3 x 360*/380/400/415 VAC (3Ph+N)
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46~54 Hz or 56~64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦2% THD (Linear load)

≦5% THD (Non-linear load)

ALARM & INDICATORS

LCD Display UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions

MANAGEMENT

Smart RS-232 / USB Support Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux and Mac
Optional SNMP Power management from SNMP manager and web browser

BATTERY

Standard Model

Type

12V Lead Acid
Numbers (10+10)pcs x 1 strings
Typical Recharge Time  4 hours recover to 90% capacity
Long-run Model

Type

Depending on customer
Numbers 1A/2A/3A/4A/5A/6A/7A/8A/9A/10A/11A/12A (Adjustable)
12A maximum
Charging Current (max) 4A
PRO83315-FS/FL 15KVA

GENERAL

UPS Type Tower
Phase 3-phase in / 3-phase out
Standard Model

Dimension (mm)

630 x 250x 750 (D x W x H)
Weight (kg) 139
Long-run Model

Dimension (mm)

630 x 250 x 750 (D x W x H)
Weight (kg) 43

INPUT

Nominal Voltage 3 x 400 VAC (3Ph+N)
Voltage Range 190-520 VAC (3-phase) @ 50% load

305-478 VAC (3-phase) @ 100% load

Frequency Range 46~54 Hz or 56~64Hz
Power Factor ≧0.99 @ 100% Load

OUTPUT

Output Voltage 3 x 360*/380/400/415 VAC (3Ph+N)
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46~54 Hz or 56~64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦2% THD (Linear load)

≦5% THD (Non-linear load)

ALARM & INDICATORS

LCD Display UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions

MANAGEMENT

Smart RS-232 / USB Support Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux and Mac
Optional SNMP Power management from SNMP manager and web browser

BATTERY

Standard Model

Type

12V Lead Acid
Numbers (16+16)pcs x 1 strings
Typical Recharge Time  4 hours recover to 90% capacity
Long-run Model

Type

Depending on customer
Numbers 1A/2A/3A/4A/5A/6A/7A/8A/9A/10A/11A/12A (Adjustable)
12A maximum
Charging Current (max) 4A
PRO83320-FS/FL 20KVA

GENERAL

UPS Type Tower
Phase 3-phase in / 3-phase out
Standard Model

Dimension (mm)

630 x 250x 750 (D x W x H)
Weight (kg) 139
Long-run Model

Dimension (mm)

630 x 250 x 750 (D x W x H)
Weight (kg) 43

INPUT

Nominal Voltage 3 x 400 VAC (3Ph+N)
Voltage Range 190-520 VAC (3-phase) @ 50% load

305-478 VAC (3-phase) @ 100% load

Frequency Range 46~54 Hz or 56~64Hz
Power Factor ≧0.99 @ 100% Load

OUTPUT

Output Voltage 3 x 360*/380/400/415 VAC (3Ph+N)
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46~54 Hz or 56~64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦2% THD (Linear load)

≦5% THD (Non-linear load)

ALARM & INDICATORS

LCD Display UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions

MANAGEMENT

Smart RS-232 / USB Support Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux and Mac
Optional SNMP Power management from SNMP manager and web browser

BATTERY

Standard Model

Type

12V Lead Acid
Numbers (16+16)pcs x 1 strings
Typical Recharge Time  4 hours recover to 90% capacity
Long-run Model

Type

Depending on customer
Numbers 1A/2A/3A/4A/5A/6A/7A/8A/9A/10A/11A/12A (Adjustable)
12A maximum
Charging Current (max) 4A
PRO83330-FS/FL 30KVA

GENERAL

UPS Type Tower
Phase 3-phase in / 3-phase out
Standard Model

Dimension (mm)

815 x 300 x 1000 (D x W x H)
Weight (kg) 152
Long-run Model

Dimension (mm)

815 x 300 x 1000 (D x W x H)
Weight (kg) 60

INPUT

Nominal Voltage 3 x 400 VAC (3Ph+N)
Voltage Range 190-520 VAC (3-phase) @ 50% load

305-478 VAC (3-phase) @ 100% load

Frequency Range 46~54 Hz or 56~64Hz
Power Factor ≧0.99 @ 100% Load

OUTPUT

Output Voltage 3 x 360*/380/400/415 VAC (3Ph+N)
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46~54 Hz or 56~64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦2% THD (Linear load)

≦5% THD (Non-linear load)

ALARM & INDICATORS

LCD Display UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions

MANAGEMENT

Smart RS-232 / USB Support Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux and Mac
Optional SNMP Power management from SNMP manager and web browser

BATTERY

Standard Model

Type

12V Lead Acid
Numbers (16+16)pcs x 2 strings
Typical Recharge Time  4 hours recover to 90% capacity
Long-run Model

Type

Depending on customer
Numbers 1A/2A/3A/4A/5A/6A/7A/8A/9A/10A/11A/12A (Adjustable)
12A maximum
Charging Current (max) 4A
PRO83340-FS/FL 40KVA

GENERAL

UPS Type Tower
Phase 3-phase in / 3-phase out
Standard Model

Dimension (mm)

815 x 300 x 1000 (D x W x H)
Weight (kg) 117
Long-run Model

Dimension (mm)

815 x 300 x 1000 (D x W x H)
Weight (kg) 61

INPUT

Nominal Voltage 3 x 400 VAC (3Ph+N)
Voltage Range 190-520 VAC (3-phase) @ 50% load

305-478 VAC (3-phase) @ 100% load

Frequency Range 46~54 Hz or 56~64Hz
Power Factor ≧0.99 @ 100% Load

OUTPUT

Output Voltage 3 x 360*/380/400/415 VAC (3Ph+N)
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46~54 Hz or 56~64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦2% THD (Linear load)

≦5% THD (Non-linear load)

ALARM & INDICATORS

LCD Display UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions

MANAGEMENT

Smart RS-232 / USB Support Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux and Mac
Optional SNMP Power management from SNMP manager and web browser

BATTERY

Standard Model

Type

12V Lead Acid
Numbers (16+16)pcs x 2 strings
Typical Recharge Time  4 hours recover to 90% capacity
Long-run Model

Type

Depending on customer
Numbers 1A/2A/3A/4A/5A/6A/7A/8A/9A/10A/11A/12A (Adjustable)
12A maximum
Charging Current (max) 4A
PRO83360-FL 60KVA

GENERAL

UPS Type Tower
Phase 3-phase in / 3-phase out
Long-run Model

Dimension (mm)

790 x 360 x 1010 (D x W x H)
Weight (kg) 108

INPUT

Nominal Voltage 3 x 400 VAC (3Ph+N)
Voltage Range 190-520 VAC (3-phase) @ 50% load

305-478 VAC (3-phase) @ 100% load

Frequency Range 46~54 Hz or 56~64Hz
Power Factor ≧0.99 @ 100% Load

OUTPUT

Output Voltage 3 x 360*/380/400/415 VAC (3Ph+N)
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46~54 Hz or 56~64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦2% THD (Linear load)

≦5% THD (Non-linear load)

ALARM & INDICATORS

LCD Display UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions

MANAGEMENT

Smart RS-232 / USB Support Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux and Mac
Optional SNMP Power management from SNMP manager and web browser

BATTERY

Long-run Model

Type

Depending on customer
Numbers N/A
Charging Current (max) 2A/4A/6A/8A/10A/11A/12A/14A/16A/18A/20A/22A/24A (Adjustable)
Parallel able up to 2 charger boards to reach 24A maximum 
PRO83380-FL 80KVA

GENERAL

UPS Type Tower
Phase 3-phase in / 3-phase out
Long-run Model

Dimension (mm)

790 x 360 x 1010 (D x W x H)
Weight (kg) 113

INPUT

Nominal Voltage 3 x 400 VAC (3Ph+N)
Voltage Range 190-520 VAC (3-phase) @ 50% load

305-478 VAC (3-phase) @ 100% load

Frequency Range 46~54 Hz or 56~64Hz
Power Factor ≧0.99 @ 100% Load

OUTPUT

Output Voltage 3 x 360*/380/400/415 VAC (3Ph+N)
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46~54 Hz or 56~64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦2% THD (Linear load)

≦5% THD (Non-linear load)

ALARM & INDICATORS

LCD Display UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions

MANAGEMENT

Smart RS-232 / USB Support Windows® 2000/2003/XP/Vista/2008, Windows® 7/8, Linux and Mac
Optional SNMP Power management from SNMP manager and web browser

BATTERY

Long-run Model

Type

Depending on customer
Numbers N/A
Charging Current (max) 2A/4A/6A/8A/10A/11A/12A/14A/16A/18A/20A/22A/24A (Adjustable)
Parallel able up to 2 charger boards to reach 24A maximum 
PRO833100-FL 100KVA

GENERAL

UPS Type Tower
Phase 3-phase in / 3-phase out
Rating (VA) 100KVA
Nominal Power (W) 90KW
Long-run Model

Dimension (mm)

940 x 567 x 1000 (D x W x H)
Weight (kg) 199

INPUT

Connection Type Terminal
Nominal Voltage 3 x 400 VAC (3Ph+N)
Voltage Range 208-478 VAC (3-phase) @ 70% load

305-478 VAC (3-phase) @ 100% load

Frequency Range 40~70Hz
Power Factor ≧0.99 @ 100% Load

OUTPUT

Connection Type Terminal
Output Voltage 3 x 380/400/415 VAC (3Ph+N)
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46-54Hz or 56-64Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦2% THD (Linear load)

≦4% THD (Non-linear load)

INDICATORS & MANAGEMENT

LCD 10" Touch Type color LCD
Smart RS-232 / USB Supports Windows® 2000/2003/XPNista/2008, Windows® 7/8, Linux and MAC
Optional SNMP Power management from SNMP manager and web browser

BATTERY

Long-run Model

Type

Depending on the capacity of external batteries
Numbers 32 ~ 40 (Adjustable)
Charging Current (max) 24A
PRO833120-FL 120KVA

GENERAL

UPS Type Tower
Phase 3-phase in / 3-phase out
Rating (VA) 120KVA
Nominal Power (W) 108KW
Long-run Model

Dimension (mm)

940 x 567 x 1000 (D x W x H)
Weight (kg) 234

INPUT

Connection Type Terminal
Nominal Voltage 3 x 400 VAC (3Ph+N)
Voltage Range 208-478 VAC (3-phase) @ 70% load

305-478 VAC (3-phase) @ 100% load

Frequency Range 40~70Hz
Power Factor ≧0.99 @ 100% Load

OUTPUT

Connection Type Terminal
Output Voltage 3 x 380/400/415 VAC (3Ph+N)
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46-54Hz or 56-64Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦2% THD (Linear load)

≦4% THD (Non-linear load)

INDICATORS & MANAGEMENT

LCD 10" Touch Type color LCD
Smart RS-232 / USB Supports Windows® 2000/2003/XPNista/2008, Windows® 7/8, Linux and MAC
Optional SNMP Power management from SNMP manager and web browser

BATTERY

Long-run Model

Type

Depending on the capacity of external batteries
Numbers 32 ~ 40 (Adjustable)
Charging Current (max) 32A
PRO833160-FL 160KVA

GENERAL

UPS Type Tower
Phase 3-phase in / 3-phase out
Rating (VA) 160KVA
Nominal Power (W) 144KW
Long-run Model

Dimension (mm)

1040 x 567 x 1452 (D x W x H)
Weight (kg) 306

INPUT

Connection Type Terminal
Nominal Voltage 3 x 400 VAC (3Ph+N)
Voltage Range 208-478 VAC (3-phase) @ 70% load

305-478 VAC (3-phase) @ 100% load

Frequency Range 40~70Hz
Power Factor ≧0.99 @ 100% Load

OUTPUT

Connection Type Terminal
Output Voltage 3 x 380/400/415 VAC (3Ph+N)
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46-54Hz or 56-64Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦2% THD (Linear load)

≦4% THD (Non-linear load)

INDICATORS & MANAGEMENT

LCD 10" Touch Type color LCD
Smart RS-232 / USB Supports Windows® 2000/2003/XPNista/2008, Windows® 7/8, Linux and MAC
Optional SNMP Power management from SNMP manager and web browser

BATTERY

Long-run Model

Type

Depending on the capacity of external batteries
Numbers 32 ~ 40 (Adjustable)
Charging Current (max) 40A
PRO833200-FL 200KVA

GENERAL

UPS Type Tower
Phase 3-phase in / 3-phase out
Rating (VA) 200KVA
Nominal Power (W) 180KW
Long-run Model

Dimension (mm)

1040 x 567 x 1452 (D x W x H)
Weight (kg) 340

INPUT

Connection Type Terminal
Nominal Voltage 3 x 400 VAC (3Ph+N)
Voltage Range 208-478 VAC (3-phase) @ 70% load

305-478 VAC (3-phase) @ 100% load

Frequency Range 40~70Hz
Power Factor ≧0.99 @ 100% Load

OUTPUT

Connection Type Terminal
Output Voltage 3 x 380/400/415 VAC (3Ph+N)
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46-54Hz or 56-64Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1 (max.)
Harmonic Distortion ≦2% THD (Linear load)

≦4% THD (Non-linear load)

INDICATORS & MANAGEMENT

LCD 10" Touch Type color LCD
Smart RS-232 / USB Supports Windows® 2000/2003/XPNista/2008, Windows® 7/8, Linux and MAC
Optional SNMP Power management from SNMP manager and web browser

BATTERY

Long-run Model

Type

Depending on the capacity of external batteries
Numbers 32 ~ 40 (Adjustable)
Charging Current (max) 48A

DOWNLOAD

Document Date Version
2017-08-07 1.00
2017-08-07 1.00