MODEL
PRO73310-ES/EL 10KVA
GENERAL
UPS Type | Tower |
Phase | 3 phase in / 3 phase out |
Rating (VA) | 10KVA |
Nominal Power (W) | 9KW |
Dimension (mm) | 770 x 450 x 1100 (D x W x H) |
Weight (kg) | 83 (without batteries) 210 (w/built-in batteries) |
INPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 400 V (3Ph+N) |
Voltage Range | +15% or –20% |
Frequency Range | 50 / 60 Hz ±5 % |
Power Factor | 1.0 |
THDi | < 1.5% @ 100% load < 2.5% @ 50% load < 6.0% @ 10% load |
INVERTER
Connection Type | Terminal |
NominalVoltage | 3 x 400 V (3Ph+N) |
Precision | Stationary: ±1% ; Transitory: ±2% (load variations 100-0-100%) |
Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
Max. Synchronisation Speed | 10 Hz/s |
Admissible Crest Factor | 3.4 : 1 |
Harmonic Distortion | < 0.5% (Linear Load) < 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
Voltage | 3 x 400V (3Ph + N) |
Frequency | 50/60 Hz |
BATTERY
Type | 12V 4.5Ah |
Back-up Time (minutes) | 5 |
Max. Charging Current | 23.5 A |
REAR PANEL
|

PRO73315-ES/EL 15KVA
GENERAL
UPS Type | Tower |
Phase | 3 phase in / 3 phase out |
Rating (VA) | 15KVA |
Nominal Power (W) | 13.5KW |
Dimension (mm) | 770 x 450 x 1100 (D x W x H) |
Weight (kg) | 88 (without batteries) 212 (w/built-in batteries) |
INPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 400 V (3Ph+N) |
Voltage Range | +15% or –20% |
Frequency Range | 50 / 60 Hz ±5 % |
Power Factor | 1.0 |
THDi | < 1.5% @ 100% load < 2.5% @ 50% load < 6.0% @ 10% load |
INVERTER
Connection Type | Terminal |
NominalVoltage | 3 x 400 V (3Ph+N) |
Precision | Stationary: ±1% ; Transitory: ±2% (load variations 100-0-100%) |
Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
Max. Synchronisation Speed | 10 Hz/s |
Admissible Crest Factor | 3.4 : 1 |
Harmonic Distortion | < 0.5% (Linear Load) < 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
Voltage | 3 x 400V (3Ph + N) |
Frequency | 50/60 Hz |
BATTERY
Type | 12V 4.5Ah |
Back-up Time (minutes) | 3 |
Max. Charging Current | 23.5 A |
REAR PANEL
|

PRO73320-ES/EL 20KVA
GENERAL
UPS Type | Tower |
Phase | 3 phase in / 3 phase out |
Rating (VA) | 20KVA |
Nominal Power (W) | 18KW |
Dimension (mm) | 770 x 450 x 1100 (D x W x H) |
Weight (kg) | 95 (without batteries) 215 (w/built-in batteries) |
INPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 400 V (3Ph+N) |
Voltage Range | +15% or –20% |
Frequency Range | 50 / 60 Hz ±5 % |
Power Factor | 1.0 |
THDi | < 1.5% @ 100% load < 2.5% @ 50% load < 6.0% @ 10% load |
INVERTER
Connection Type | Terminal |
NominalVoltage | 3 x 400 V (3Ph+N) |
Precision | Stationary: ±1% ; Transitory: ±2% (load variations 100-0-100%) |
Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
Max. Synchronisation Speed | 10 Hz/s |
Admissible Crest Factor | 3.4 : 1 |
Harmonic Distortion | < 0.5% (Linear Load) < 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
Voltage | 3 x 400V (3Ph + N) |
Frequency | 50/60 Hz |
BATTERY
Type | 12V 7Ah |
Back-up Time (minutes) | 5 |
Max. Charging Current | 23.5 A |
REAR PANEL
|

PRO73330-ES/EL 30KVA
GENERAL
UPS Type | Tower |
Phase | 3 phase in / 3 phase out |
Rating (VA) | 30KVA |
Nominal Power (W) | 27KW |
Dimension (mm) | 770 x 450 x 1100 (D x W x H) |
Weight (kg) | 113 (without batteries) 310 (w/built-in batteries) |
INPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 400 V (3Ph+N) |
Voltage Range | +15% or –20% |
Frequency Range | 50 / 60 Hz ±5 % |
Power Factor | 1.0 |
THDi | < 1.0% @ 100% load < 2.0% @ 50% load < 5.0% @ 10% load |
INVERTER
Connection Type | Terminal |
NominalVoltage | 3 x 400 V (3Ph+N) |
Precision | Stationary: ±1% ; Transitory: ±2% (load variations 100-0-100%) |
Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
Max. Synchronisation Speed | 10 Hz/s |
Admissible Crest Factor | 3.2 : 1 |
Harmonic Distortion | < 0.5% (Linear Load) < 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
Voltage | 3 x 400V (3Ph + N) |
Frequency | 50/60 Hz |
BATTERY
Type | 12V 9Ah |
Back-up Time (minutes) | 3 |
Max. Charging Current | 23.5 A |
REAR PANEL
|

PRO73340-ES/EL 40KVA
GENERAL
UPS Type | Tower |
Phase | 3 phase in / 3 phase out |
Rating (VA) | 40KVA |
Nominal Power (W) | 36KW |
Dimension (mm) | 770 x 450 x 1100 (D x W x H) |
Weight (kg) | 120 (without batteries) 400 (w/built-in batteries) |
INPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 400 V (3Ph+N) |
Voltage Range | +15% or –20% |
Frequency Range | 50 / 60 Hz ±5 % |
Power Factor | 1.0 |
THDi | < 1.0% @ 100% load < 2.0% @ 50% load < 5.0% @ 10% load |
INVERTER
Connection Type | Terminal |
NominalVoltage | 3 x 400 V (3Ph+N) |
Precision | Stationary: ±1% ; Transitory: ±2% (load variations 100-0-100%) |
Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
Max. Synchronisation Speed | 10 Hz/s |
Admissible Crest Factor | 3.2 : 1 |
Harmonic Distortion | < 0.5% (Linear Load) < 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
Voltage | 3 x 400V (3Ph + N) |
Frequency | 50/60 Hz |
BATTERY
Type | 12V 12Ah |
Back-up Time (minutes) | 3 |
Max. Charging Current | 47 A |
REAR PANEL
|

PRO73360-EL 60KVA
GENERAL
UPS Type | Tower |
Phase | 3 phase in / 3 phase out |
Rating (VA) | 60KVA |
Nominal Power (W) | 54KW |
Dimension (mm) | 770 x 450 x 1100 (D x W x H) |
Weight (kg) | 185 (without batteries) |
INPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 400 V (3Ph+N) |
Voltage Range | +15% or –20% |
Frequency Range | 50 / 60 Hz ±5 % |
Power Factor | 1.0 |
THDi | < 1.0% @ 100% load < 2.0% @ 50% load < 5.0% @ 10% load |
INVERTER
Connection Type | Terminal |
NominalVoltage | 3 x 400 V (3Ph+N) |
Precision | Stationary: ±1% ; Transitory: ±2% (load variations 100-0-100%) |
Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
Max. Synchronisation Speed | 10 Hz/s |
Admissible Crest Factor | 3.2 : 1 |
Harmonic Distortion | < 0.5% (Linear Load) < 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
Voltage | 3 x 400V (3Ph + N) |
Frequency | 50/60 Hz |
BATTERY
Type | - |
Back-up Time (minutes) | - |
Max. Charging Current | 47 A |
REAR PANEL
|

PRO73380-EL 80KVA
GENERAL
UPS Type | Tower |
Phase | 3 phase in / 3 phase out |
Rating (VA) | 80KVA |
Nominal Power (W) | 72KW |
Dimension (mm) | 805 x 590 x 1320 (D x W x H) |
Weight (kg) | 265 (without batteries) |
INPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 400 V (3Ph+N) |
Voltage Range | +15% or –20% |
Frequency Range | 50 / 60 Hz ±5 % |
Power Factor | 1.0 |
THDi | < 1.0% @ 100% load < 2.0% @ 50% load < 5.0% @ 10% load |
INVERTER
Connection Type | Terminal |
NominalVoltage | 3 x 400 V (3Ph+N) |
Precision | Stationary: ±1% ; Transitory: ±2% (load variations 100-0-100%) |
Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
Max. Synchronisation Speed | 10 Hz/s |
Admissible Crest Factor | 2.8 : 1 |
Harmonic Distortion | < 0.5% (Linear Load) < 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
Voltage | 3 x 400V (3Ph + N) |
Frequency | 50/60 Hz |
BATTERY
Type | - |
Back-up Time (minutes) | - |
Max. Charging Current | 70.5 A |
REAR PANEL
|

PRO733100-EL 100KVA
GENERAL
UPS Type | Tower |
Phase | 3 phase in / 3 phase out |
Rating (VA) | 100KVA |
Nominal Power (W) | 90KW |
Dimension (mm) | 805 x 590 x 1320 (D x W x H) |
Weight (kg) | 290 (without batteries) |
INPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 400 V (3Ph+N) |
Voltage Range | +15% or –20% |
Frequency Range | 50 / 60 Hz ±5 % |
Power Factor | 1.0 |
THDi | < 1.5% @ 100% load < 2.0% @ 50% load < 6.0% @ 10% load |
INVERTER
Connection Type | Terminal |
NominalVoltage | 3 x 400 V (3Ph+N) |
Precision | Stationary: ±1% ; Transitory: ±2% (load variations 100-0-100%) |
Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
Max. Synchronisation Speed | 10 Hz/s |
Admissible Crest Factor | 3.2 : 1 |
Harmonic Distortion | < 0.5% (Linear Load) < 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
Voltage | 3 x 400V (3Ph + N) |
Frequency | 50/60 Hz |
BATTERY
Type | - |
Back-up Time (minutes) | - |
Max. Charging Current | 70.5 A |
REAR PANEL
|

PRO733120-EL 120KVA
GENERAL
UPS Type | Tower |
Phase | 3 phase in / 3 phase out |
Rating (VA) | 120KVA |
Nominal Power (W) | 108KW |
Dimension (mm) | 805 x 590 x 1320 (D x W x H) |
Weight (kg) | 290 (without batteries) |
INPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 400 V (3Ph+N) |
Voltage Range | +15% or –20% |
Frequency Range | 50 / 60 Hz ±5 % |
Power Factor | 1.0 |
THDi | < 1.5% @ 100% load < 2.0% @ 50% load < 6.0% @ 10% load |
INVERTER
Connection Type | Terminal |
NominalVoltage | 3 x 400 V (3Ph+N) |
Precision | Stationary: ±1% ; Transitory: ±2% (load variations 100-0-100%) |
Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
Max. Synchronisation Speed | 10 Hz/s |
Admissible Crest Factor | 3.2 : 1 |
Harmonic Distortion | < 0.5% (Linear Load) < 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
Voltage | 3 x 400V (3Ph + N) |
Frequency | 50/60 Hz |
BATTERY
Type | - |
Back-up Time (minutes) | - |
Max. Charging Current | 188 A |
REAR PANEL
|

PRO733160-EL 160KVA
GENERAL
UPS Type | Tower |
Phase | 3 phase in / 3 phase out |
Rating (VA) | 160KVA |
Nominal Power (W) | 144KW |
Dimension (mm) | 850 x 900 x 1900 (D x W x H) |
Weight (kg) | 540 (without batteries) |
INPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 400 V (3Ph+N) |
Voltage Range | +15% or –20% |
Frequency Range | 50 / 60 Hz ±5 % |
Power Factor | 1.0 |
THDi | < 1.5% @ 100% load < 2.0% @ 50% load < 6.0% @ 10% load |
INVERTER
Connection Type | Terminal |
NominalVoltage | 3 x 400 V (3Ph+N) |
Precision | Stationary: ±1% ; Transitory: ±2% (load variations 100-0-100%) |
Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
Max. Synchronisation Speed | 10 Hz/s |
Admissible Crest Factor | 3.0 : 1 |
Harmonic Distortion | < 0.5% (Linear Load) < 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
Voltage | 3 x 400V (3Ph + N) |
Frequency | 50/60 Hz |
BATTERY
Type | - |
Back-up Time (minutes) | - |
Max. Charging Current | 188 A |
REAR PANEL
1. Relay interface 2. Emergency Power Off (EPO) 3. RS-232 COM ports 4. Intelligent Slot 5. Input circuit breaker 6. Maintenance bypass switch 7. Output switch 8. Battery switch 10. Parallel port (only available for parallel configuration) |

PRO733200-EL 200KVA
GENERAL
UPS Type | Tower |
Phase | 3 phase in / 3 phase out |
Rating (VA) | 200KVA |
Nominal Power (W) | 180KW |
Dimension (mm) | 850 x 900 x 1900 (D x W x H) |
Weight (kg) | 550 (without batteries) |
INPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 400 V (3Ph+N) |
Voltage Range | +15% or –20% |
Frequency Range | 50 / 60 Hz ±5 % |
Power Factor | 1.0 |
THDi | < 1.5% @ 100% load < 2.0% @ 50% load < 6.0% @ 10% load |
INVERTER
Connection Type | Terminal |
NominalVoltage | 3 x 400 V (3Ph+N) |
Precision | Stationary: ±1% ; Transitory: ±2% (load variations 100-0-100%) |
Frequency | 50/60 Hz synchronised ±4 % With mains absent ±0.05% |
Max. Synchronisation Speed | 10 Hz/s |
Admissible Crest Factor | 3.0 : 1 |
Harmonic Distortion | < 0.5% (Linear Load) < 1.5% (Non-linear Load) |
MAINTENANCE BYPASS
Voltage | 3 x 400V (3Ph + N) |
Frequency | 50/60 Hz |
BATTERY
Type | - |
Back-up Time (minutes) | - |
Max. Charging Current | 188 A |
REAR PANEL
1. Relay interface 2. Emergency Power Off (EPO) 3. RS-232 COM ports 4. Intelligent Slot 5. Input circuit breaker 6. Maintenance bypass switch 7. Output switch 8. Battery switch 10. Parallel port (only available for parallel configuration) |