Professional I Series (1P/1P)

PRO900-VS/VL SERIES 1-3KVA

True Double-Conversion Online UPS

Mircoprocessor control optimizes reliability

Input power factor correction

Output Power Factor 0.8

Converter mode available

Wide input voltage (110V - 300V)

MODEL

PRO901-VS/VL 1KVA

GENERAL

UPS Type Tower
Phase Single phase with ground
Rating (VA) 1000
Nominal Power (W) 800
Standard Model Dimension (mm) 282 x 145 x 220 (D x W x H)
Weight (kg) 9.8
Long-run Model Dimension (mm) 282 x 145 x 220 (D x W x H)
Weight (kg) 4.1

INPUT

Connection Type IEC 320-C14
Nominal Voltage 200/208/220/230/240 VAC
Voltage Range 110-300 VAC (Load at 50%) 160-280 VAC (Load at 100%)
Frequency Range 45 ~ 70 Hz
Power Factor ≥ 0.99

OUTPUT

Connection Type 3 x IEC 320-C13
Nominal Voltage 200/208/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≤3% THD (Linear load) ≤6% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
LED Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys
Communication Smart RS232* Emergency Power Off (EPO) (Optional)

BATTERY

Standard Model Type 12V / 9Ah
Numbers 2
Typical Recharge Time  4 hours recover to 90% capacity
Long-run Model Type Dependent
Number 2 or 3
Charging Current (max) 1A / 2A / 4A / 6A Adjustable

REAR PANEL

1. AC Input 2. Input circuit breaker 3. RS-232 communication port 4. External battery connection (Only available for L model) 5 Output receptacles
PRO902-VS/VL 2KVA

GENERAL

UPS Type Tower
Phase Single phase with ground
Rating (VA) 2000
Nominal Power (W) 1600
Standard Model Dimension (mm) 397 x 145 x 220 (D x W x H)
Weight (kg) 17
Long-run Model Dimension (mm) 397 x 145 x 220 (D x W x H)
Weight (kg) 6.8

INPUT

Connection Type IEC 320-C14
Nominal Voltage 200/208/220/230/240 VAC
Voltage Range 110-300 VAC (Load at 50%) 160-280 VAC (Load at 100%)
Frequency Range 45 ~ 70 Hz
Power Factor ≥ 0.99

OUTPUT

Connection Type 4 x IEC 320-C13
Nominal Voltage 200/208/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≤3% THD (Linear load) ≤6% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
LED Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys
Communication Smart RS232* Emergency Power Off (EPO) (Optional)

BATTERY

Standard Model Type 12V / 9Ah
Numbers 4
Typical Recharge Time  4 hours recover to 90% capacity
Long-run Model Type Dependent
Number 4 / 6 / 8
Charging Current (max) 1A / 2A / 4A / 6A Adjustable

REAR PANEL

1. AC Input 2. Input circuit breaker 3. RS-232 communication port 4. External battery connection (Only available for L model) 5 Output receptacles
PRO903-VS/VL 3KVA

GENERAL

UPS Type Tower
Phase Single phase with ground
Rating (VA) 3000
Nominal Power (W) 2400
Standard Model Dimension (mm) 421 x 190 x 318 (D x W x H)
Weight (kg) 27.6
Long-run Model Dimension (mm) 397 x 145 x 220 (D x W x H)
Weight (kg) 7.4

INPUT

Connection Type IEC 320-C20
Nominal Voltage 200/208/220/230/240 VAC
Voltage Range 110-300 VAC (Load at 50%) 160-280 VAC (Load at 100%)
Frequency Range 45 ~ 70 Hz
Power Factor ≥ 0.99

OUTPUT

Connection Type 4 x IEC 320-C13
Nominal Voltage 200/208/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≤3% THD (Linear load) ≤6% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
LED Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys
Communication Smart RS232* Emergency Power Off (EPO) (Optional)

BATTERY

Standard Model Type 12V / 9Ah
Numbers 6
Typical Recharge Time  4 hours recover to 90% capacity
Long-run Model Type Dependent
Number 6 or 8
Charging Current (max) 1A / 2A / 4A / 6A Adjustable

REAR PANEL

1. AC Input 2. Input circuit breaker 3. RS-232 communication port 4. External battery connection (Only available for L model) 5 Output receptacles 6. Output terminal (Only available for 3KVA)

DOWNLOAD

Document Date Version
2015-01-31 1.00
2020-07-27 1.10
2020-08-06 1.10