Professional II Series (3P/1P)

PRO93100-WS/WL SERIES 10-20KVA

Generator compatible

True Double-Conversion

Output power factor 0.8

Emergency power off function (EPO)

Wide input voltage range

Optional maintenance bypass switch

MODEL

PRO93110-WS/WL 10KVA

GENERAL

UPS Type Tower
Phase 3 phase in / 1 phase out
Rating (VA) 10000
Nominal Power (W) 8000
Standard Model

Dimension (mm)

442 x 190 x 688 (D x W x H)
Weight (kg) 76
Long-run Model

Dimension (mm)

442 x 190 x 318 (D x W x H)
Weight (kg) 15

INPUT

Connection Type Terminal
Nominal Voltage 3 x 400 VAC (3Ph+N)
Voltage Range 190-520 VAC (3-phase) @ 50% load

305-520 VAC (3-phase) @ 100% load

Frequency Range 46~54 Hz

OUTPUT

Connection Type Terminal
Nominal Voltage 208/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46 Hz ~ 54 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≤3% THD (Linear load)

≤5% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
LCD Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

Standard Model

Type

12V / 9Ah
Numbers 20
Typical Recharge Time  9 hours recover to 90% capacity
Long-run Model

Type

Depending on the capacity of external batteries
Number 16 or 20
Charging Current (max) 4A Default, 1A/2A/4A (Adjustable)

REAR PANEL

  1.  External battery connection
  2. RS-232 communication port
  3. Intelligent slot
  4. USB communication port
  5. Emergency power off function connector (EPO connector)
  6. Cooling fan
  7. Input circuit breaker
  8. Maintenance bypass switch (optional)
  9. Output terminal
  10. Grounding terminal
  11. Utility input terminal
PRO93115-WS/WL 15KVA

GENERAL

UPS Type Tower
Phase 3 phase in / 1 phase out
Rating (VA) 15000
Nominal Power (W) 12000
Standard Model

Dimension (mm)

442 x 190 x 688 (D x W x H)
Weight (kg) 78
Long-run Model

Dimension (mm)

442 x 190 x 318 (D x W x H)
Weight (kg) 16

INPUT

Connection Type Terminal
Nominal Voltage 3 x 400 VAC (3Ph+N)
Voltage Range 190-520 VAC (3-phase) @ 50% load

305-520 VAC (3-phase) @ 100% load

Frequency Range 46~54 Hz

OUTPUT

Connection Type Terminal
Nominal Voltage 208/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46 Hz ~ 54 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≤3% THD (Linear load)

≤5% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
LCD Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

Standard Model

Type

12V / 9Ah
Numbers 20
Typical Recharge Time  9 hours recover to 90% capacity
Long-run Model

Type

Depending on the capacity of external batteries
Number 16 or 20
Charging Current (max) 4A Default, 1A/2A/4A (Adjustable)

REAR PANEL

  1.  External battery connection
  2. RS-232 communication port
  3. Intelligent slot
  4. USB communication port
  5. Emergency power off function connector (EPO connector)
  6. Cooling fan
  7. Input circuit breaker
  8. Maintenance bypass switch (optional)
  9. Output terminal
  10. Grounding terminal
  11. Utility input terminal
PRO93120-WS/WL 20KVA

GENERAL

UPS Type Tower
Phase 3 phase in / 1 phase out
Rating (VA) 20000
Nominal Power (W) 16000
Standard Model

Dimension (mm)

815 x 250x 826 (D x W x H)
Weight (kg) 145
Long-run Model

Dimension (mm)

575 x 190 x 318 (D x W x H)
Weight (kg) 18.95

INPUT

Connection Type Terminal
Nominal Voltage 3 x 400 VAC (3Ph+N)
Voltage Range 190-520 VAC (3-phase) @ 50% load

305-520 VAC (3-phase) @ 100% load

Frequency Range 46~54 Hz

OUTPUT

Connection Type Terminal
Nominal Voltage 208/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46 Hz ~ 54 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≤3% THD (Linear load)

≤5% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
LCD Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

Standard Model

Type

12V / 9Ah
Numbers 20 x 2 strings
Typical Recharge Time  9 hours recover to 90% capacity
Long-run Model

Type

Depending on the capacity of external batteries
Number 16 or 20
Charging Current (max) 4A Default, 1A/2A/4A (Adjustable)

REAR PANEL

  1.  External battery connection
  2. RS-232 communication port
  3. Intelligent slot
  4. USB communication port
  5. Emergency power off function connector (EPO connector)
  6. Cooling fan
  7. Input circuit breaker
  8. Maintenance bypass switch (optional)
  9. Output terminal
  10. Grounding terminal
  11. Utility input terminal

DOWNLOAD

Document Date Version
2015-01-31 1.00
2017-08-07 1.00
2017-08-07 1.00

You may also like…

PRO900-ES/EL SERIES 1-10KVA

PRO900-WRS/WRL SERIES 1-10KVA

PRO900-WS/WL SERIES 1-10KVA

PRO900-VS/VL SERIES 1-3KVA

PRO900-ERS/ERL SERIES 1-10KVA