MODEL

PRO901-WRS/WRL 1KVA

GENERAL

UPS Type Rack / Tower
Phase Single phase with ground
Rating (VA) 1000
Nominal Power (W) 800
Standard Model Dimension (mm) 310 x 438 x 88 [2U] (D x W x H)
Weight (kg) 12
Long-run Model Dimension (mm) 310 x 438 x 88 [2U] (D x W x H)
Weight (kg) 9

INPUT

Connection Type IEC 320-C14
Nominal Voltage 200/208/220/230/240 VAC
Voltage Range 110-300 VAC (Load at 50%) 160-280 VAC (Load at 100%)
Frequency Range 40 ~ 70 Hz
Power Factor ≥ 0.99

OUTPUT

Connection Type 3 x IEC 320-C13
Nominal Voltage 200/208/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≤3% THD (Linear load) ≤6% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
LCD Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232* USB Port

BATTERY

Standard Model Type 12V / 9Ah
Numbers 2
Typical Recharge Time  4 hours recover to 90% capacity
Long-run Model Type Depending on the capacity of external batteries
Number 2 or 3
Charging Current (max) 1A / 2A / 4A / 6A Adjustable

REAR PANEL

1. AC Input 2. Input circuit breaker 3. USB Communication port 4. RS-232 communication port 5.  Intelligent slot 6. External battery connection (Only available for L model) 7. Output receptacles
PRO902-WRS/WRL 2KVA

GENERAL

UPS Type Rack / Tower
Phase Single phase with ground
Rating (VA) 2000
Nominal Power (W) 1600
Standard Model Dimension (mm) 410 x 438 x 88 [2U] (D x W x H)
Weight (kg) 19
Long-run Model Dimension (mm) 410 x 438 x 88 [2U] (D x W x H)
Weight (kg) 12

INPUT

Connection Type IEC 320-C14
Nominal Voltage 200/208/220/230/240 VAC
Voltage Range 110-300 VAC (Load at 50%) 160-280 VAC (Load at 100%)
Frequency Range 40 ~ 70 Hz
Power Factor ≥ 0.99

OUTPUT

Connection Type 4 x IEC 320-C13
Nominal Voltage 200/208/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≤3% THD (Linear load) ≤6% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
LCD Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232* USB Port

BATTERY

Standard Model Type 12V / 9Ah
Numbers 4
Typical Recharge Time  4 hours recover to 90% capacity
Long-run Model Type Depending on the capacity of external batteries
Number 4 / 6 / 8
Charging Current (max) 1A / 2A / 4A / 6A Adjustable

REAR PANEL

1. AC Input 2. Input circuit breaker 3. USB Communication port 4. RS-232 communication port 5.  Intelligent slot 6. External battery connection (Only available for L model) 7. Output receptacles
PRO903-WRS/WRL 3KVA

GENERAL

UPS Type Rack / Tower
Phase Single phase with ground
Rating (VA) 3000
Nominal Power (W) 2400
Standard Model Dimension (mm) 630 x 438 x 88 [2U] (D x W x H)
Weight (kg) 29.3
Long-run Model Dimension (mm) 410 x 438 x 88 [2U] (D x W x H)
Weight (kg) 14.2

INPUT

Connection Type IEC 320-C20
Nominal Voltage 200/208/220/230/240 VAC
Voltage Range 110-300 VAC (Load at 50%) 160-280 VAC (Load at 100%)
Frequency Range 40 ~ 70 Hz
Power Factor ≥ 0.99

OUTPUT

Connection Type 4 x IEC 320-C13 Terminal
Nominal Voltage 200/208/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.25 Hz or 60 Hz ± 0.3 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≤3% THD (Linear load) ≤6% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
LCD Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232* USB Port

BATTERY

Standard Model Type 12V / 9Ah
Numbers 6
Typical Recharge Time  4 hours recover to 90% capacity
Long-run Model Type Depending on the capacity of external batteries
Number 6 or 8
Charging Current (max) 1A / 2A / 4A / 6A Adjustable

REAR PANEL

1. AC Input 2. Input circuit breaker 3. USB Communication port 4. RS-232 communication port 5.  Intelligent slot 6. External battery connection (Only available for L model) 7. Output receptacles 8. Output terminal
PRO906-WRS/WRL 6KVA

GENERAL

UPS Type Rack / Tower
Phase Single phase with ground
Rating (VA) 6000
Nominal Power (W) 4800
Standard Model Dimension (mm) UPS Unit: 530 x 438 x 88 [2U] (D x W x H) Battery Pack: 668 x 438 x 88 [2U] (D x W x H)
Weight (kg) UPS Unit: 15 Battery Pack: 48
Long-run Model Dimension (mm) 530 x 438 x 88 [2U] (D x W x H)
Weight (kg) 15

INPUT

Connection Type Terminal
Nominal Voltage 208/220/230/240 VAC
Voltage Range 110-300 VAC ± 3% at 50% Load 176-300 VAC ± 3% at 100% Load
Frequency Range 46Hz ~ 54 Hz or 56Hz ~ 64 Hz
Power Factor ≥ 0.99

OUTPUT

Connection Type Terminal
Nominal Voltage 208/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≤3% THD (Linear load) ≤5% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
LCD Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232* USB Port Emergency Power Off (EPO)

BATTERY

Standard Model Type 12V / 9Ah
Numbers 16
Typical Recharge Time  9 hours recover to 90% capacity
Long-run Model Type Depending on the capacity of external batteries
Number 16 - 20 pcs (Adjustable)
Charging Current (max) 1A/2A/4A/6A (Adjustable, 6A is only available for 16pcs batteries)

REAR PANEL

  1. External battery connector
  2. RS-232 communication port
  3. Intelligent slow
  4. USB Communication port
  5. Emergency power off function connector (EPO connector)
  6. Input circuit breaker
  7. Input/output terminal
PRO910-WRS/WRL 10KVA

GENERAL

UPS Type Rack / Tower
Phase Single phase with ground
Rating (VA) 10000
Nominal Power (W) 8000
Standard Model Dimension (mm) UPS Unit: 580 x 438 x 133 [3U] (D x W x H) Battery Pack: 580 x 438 x 133 [3U] (D x W x H)
Weight (kg) UPS Unit: 18 Battery Pack: 51
Long-run Model Dimension (mm) 530 x 438 x 133 [3U] (W x D x H)
Weight (kg) 18

INPUT

Connection Type Terminal
Nominal Voltage 208/220/230/240 VAC
Voltage Range 110-300 VAC ± 3% at 50% Load 176-300 VAC ± 3% at 100% Load
Frequency Range 46Hz ~ 54 Hz or 56Hz ~ 64 Hz
Power Factor ≥ 0.99

OUTPUT

Connection Type Terminal
Nominal Voltage 208/220/230/240 VAC
Voltage Regulation ±1%
Frequency Range (Synchronized Range) 46 Hz ~ 54 Hz or 56 Hz ~ 64 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distortion ≤3% THD (Linear load) ≤5% THD (Non-linear load)

ALARM & INDICATORS

Battery Mode Sounding every 4 seconds
Low Battery Sounding every second
Overload Sounding twice every second
Fault Continuously sounding
LCD Load level, Battery Level, AC mode, Battery mode, Bypass mode and Fault

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232* USB Port Emergency Power Off (EPO)

BATTERY

Standard Model Type 12V / 9Ah
Numbers 16
Typical Recharge Time  9 hours recover to 90% capacity
Long-run Model Type Depending on the capacity of external batteries
Number 16 - 20 pcs (Adjustable)
Charging Current (max) 1A/2A/4A/6A (Adjustable, 6A is only available for 16pcs batteries)

REAR PANEL

  1. External battery connector
  2. RS-232 communication port
  3. Intelligent slow
  4. USB Communication port
  5. Emergency power off function connector (EPO connector)
  6. Input circuit breaker
  7. Input/output terminal

DOWNLOAD

Document Date Version
2015-01-31 1.00
2020-07-27 1.10
2017-08-07 1.00
2019-09-19 2.00
2019-11-21 2.00

You may also like…

PRO900-VS/VL SERIES 1-3KVA

PRO900-WS/WL SERIES 1-10KVA