Pure Sinewave Inverter Series

IPS Series 3KVA-5KVA

MODEL

IPS3001

GENERAL

Rated Power 2.4KW/3KVA
Dimension (mm) 330 x 268 x 76 (D x W x H)
Weight (kg) 5.0KG

INPUT

Nominal Input Voltage 230Vac
Input voltage range

175Vac - 280Vac (Normal) 

90Vac - 280Vac (Generator/Wide)

Max AC Input Voltage 300Vac RMS
Nominal Input Frequency

50Hz / 60Hz (Auto detection)

Input voltage waveform

Sinusoidal

OUTPUT

Wave from Pure sine wave (Inverter mode)
Voltage Regulation (Inverter Mode) ±10% RMS
Output Frequency 50Hz / 60Hz ± 1Hz
Nominal Efficiency 90% peak
Capable of starting electric motor 1.5HP
Over-Load Protection

fault after 10s@110%~150% load

fault after 5s@≥150% load,<=200% load

Transfer Time (AC to DC)

Normal range : 10ms (typical) 15ms (max)

Generator/wide range: 20ms (typical) 40ms (max)

BATTERY & ALARM

Battery Voltage 24.0Vdc ± 0.6Vdc
Battery low alarm voltage

21.0Vdc ± 0.6Vdc

Battery low shut-down voltage 20.0Vdc ± 0.6Vdc
Battery high voltage protection (fault)

58.0Vdc

Low Battery at Inverter Mode Beep 1time every 2s
Overload

110%~150%load: beep 10s every 0.5s

>150% load: beep 5s every 0.5s then fault.

Fault Continuously beep

CHARGER

Charger Current 10A/20A selectable 10A @Vi/p<170Vac or Vi/p>280Vac; 20A@Vi/p=230Vac
Boost charger voltage (bat. Type) 28.8Vdc (Flooded); 28.2Vdc (AGM / Gel)
Floating charger voltage (bat. Type) 27.4Vdc (Flooded); 27.4Vdc (AGM / Gel)
Over charger Voltage 30.0Vdc

Real Panel

1. Battery connector

2. Input protector

3. AC input

4. Inverter output

IPS5001

GENERAL

Rated Power 4.2KW/5KVA
Dimension (mm) 407 x 350 x 110 (D x W x H)
Weight (kg) 9.2KG

INPUT

Nominal Input Voltage 230Vac
Input voltage range

175Vac - 280Vac (Normal) 

90Vac - 280Vac (Generator/Wide)

Max AC Input Voltage 300Vac RMS
Nominal Input Frequency

50Hz / 60Hz 

Input voltage waveform

Sinusoidal

OUTPUT

Wave from Pure sine wave (Inverter mode)
Voltage Regulation (Inverter Mode) ±10% RMS
Output Frequency 50Hz / 60Hz ± 1Hz
Nominal Efficiency 90% peak
Capable of starting electric motor 2.5HP
Over-Load Protection

Fault after 5s@≥150% load

Fault after 10s@110%~150% load

Transfer Time (AC to DC)

Normal range : 10ms (typical) 15ms (max)

Generator/wide range: 20ms (typical) 40ms (max)

BATTERY & ALARM

Battery Voltage 48.0VDC
Battery low alarm voltage

42.0VDC

Battery low shut-down voltage 40.0VDC
Battery high voltage protection (fault)

58.0VDC

Low Battery at Inverter Mode Beep 1time every 2s
Overload

110%~150%load: beep 10s every 0.5s

>150% load: beep 5s every 0.5s then fault.

Fault Continuously beep

CHARGER

Charger Current 25A @180V~280V; 20A @90V~180V
Boost charger voltage (bat. Type) 57.6VDC (Flooded); 56.4VDC (AGM / Gel)
Floating charger voltage (bat. Type) 54.8VDC (Flooded); 54VDC (AGM / Gel)
Over charger Voltage 60.0VDC

Real Panel

1. Battery connector

2. Input protector

3. AC input

4. Inverter output