Simulated Sinewave Inverter Series

IPS Series 1.2KVA-2.4KVA

MODEL

IPS1200

GENERAL

Capacity 1200VA
Dimension (mm) 293 x 231.5 x 82.5 (D x W x H)
Weight (kg) 2.35

INPUT

Nominal Voltage 220/ 230/ 240 VAC
Voltage Range

170-280 VAC (For Personal Computers)

90-280 VAC (For Home Appliances)

Frequency Range 50/60 Hz (Auto Sensing)

OUTPUT

AC Voltage Regulation (Batt. Mode) 230VAC ± 10%
Transfer Time 10 ms (Typical) 20 ms (max)
Waveform (Batt. Mode) Simulated Sinewave
Peak Efficiency >95%

BATTERY & PROTECTION

Battery Voltage  
Floating Charge Voltage 13.7 VDC ± 0.25 VDC
Overcharge Protection 15 VDC
Maximum Charge Current 10A or 20A (Selectable)
Full Protection Overload and short circuit protection

INDICATORS & ALARM

LCD Display Input Voltage, Output Voltage,
Load level, Battery level and Fault alarm
LED Display

Fault: Red Lighting

Battery Mode: Yellow Flashing

Low Battery: Yellow Flashing

Shutdown Mode: Yellow Flashing

Charging Mode: Green Flashing

Overload: Red Lighting

Low Battery Sounding every 2 seconds
Overload Sounding every 0.5 second
Fault Continuously sounding
Battery Replacement Not Applicable

Real Panel

1. Output receptacles

2. Operation mode selector

4. AC input

5. Input breaker

6. External battery connectors

7. Solar panel terminal (option)

8. Solar charging indicator connection (option)

IPS2400

GENERAL

Capacity 2400VA
Dimension (mm) 293 x 231.5 x 82.5 (D x W x H)
Weight (kg) 2.55

INPUT

Nominal Voltage 220/ 230/ 240 VAC
Voltage Range

170-280 VAC (For Personal Computers)

90-280 VAC (For Home Appliances)

Frequency Range 50/60 Hz (Auto Sensing)

OUTPUT

AC Voltage Regulation (Batt. Mode) 230VAC ± 10%
Transfer Time 10 ms (Typical) 20 ms (max)
Waveform (Batt. Mode) Simulated Sinewave
Peak Efficiency >95%

BATTERY & PROTECTION

Battery Voltage 24 VDC
Floating Charge Voltage 27.4 VDC ± 0.5 VDC
Overcharge Protection 30 VDC
Maximum Charge Current 10A or 20A (Selectable)
Full Protection Overload and short circuit protection

INDICATORS & ALARM

LCD Display Input Voltage, Output Voltage,
Load level, Battery level and Fault alarm
LED Display

Fault: Red Lighting

Battery Mode: Yellow Flashing

Low Battery: Yellow Flashing

Shutdown Mode: Yellow Flashing

Charging Mode: Green Flashing

Overload: Red Lighting

Low Battery Sounding every 2 seconds
Overload Sounding every 0.5 second
Fault Continuously sounding
Battery Replacement Not Applicable

Real Panel

1. Output receptacles

2. Operation mode selector

4. AC input

5. Input breaker

6. External battery connectors

7. Solar panel terminal (option)

8. Solar charging indicator connection (option)

DOWNLOAD

Document Date Version
2017-08-07 1.00
2017-08-07 1.00