MODEL
PRO53310-QRS 10KVA
GENERAL
UPS Type | Tower |
Phase | 3 phase in / 3 phase out |
Rating (VA) | 10KVA |
Nominal Power (W) | 10KW |
Dimension (mm) | 615 x 418 x 132 [3U] (D x W x H) |
Weight (kgs) | 22 |
INPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 360VAC / 380VAC / 400VAC / 415VAC (3Ph+N+PE) |
Voltage Range | 190-520 VAC (3-phase) @ 50% load
305-478 VAC (3-phase) @ 100% load |
Frequency Range | 40 Hz ~ 70 Hz |
Power Factor | ≧ 0.99 @ 100% load |
THDi | < 4% @ full linear load |
OUTPUT
Connection Type | Terminal |
Output Voltage | 360VAC / 380VAC / 400VAC / 415VAC (3Ph+N) |
Voltage Regulation | ±1% |
Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz |
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz |
Current Crest Ratio | 3:1 |
Harmonic Distortion | ≦2% THD (Linear load)
≦3% THD (Non-linear load) |
EFFICIENCY & INDICATORS
AC Mode | 94% |
ECO Mode | 97% |
At Full Load | 91% |
Peak | 92% |
LCD | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
CONNECTIVITY, CONTROL & MONITORING
Front panel | Status LED, Function keys, LCD display |
Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
Battery Voltage | ± 12V / 9 Ah |
Numbers | 16 ~ 20 pcs (adjustable) x 2 |
Typical Recharge Time | 9 hours recover to 90% capacity |
Charging Current | ± 4A |
PRO53110-QRS 10KVA
GENERAL
UPS Type | Tower |
Phase | 3 phase in / 1 phase out |
Rating (VA) | 10KVA |
Nominal Power (W) | 10KW |
Dimension (mm) | 615 x 418 x 132 [3U] (D x W x H) |
Weight (kgs) | 22 |
INPUT
Connection Type | Terminal |
Nominal Voltage | 3 x 360VAC / 380VAC / 400VAC / 415VAC (3Ph+N+PE) |
Voltage Range | 190-520 VAC (3-phase) @ 50% load
305-478 VAC (3-phase) @ 100% load |
Frequency Range | 40 Hz ~ 70 Hz |
Power Factor | ≧ 0.99 @ 100% load |
THDi | < 4% @ full linear load |
OUTPUT
Connection Type | Terminal |
Output Voltage | 208* / 220 / 230 / 240 VAC(L+N) |
Voltage Regulation | ±1% |
Frequency Range (Synchronized Range) | 46~54Hz or 56~64Hz |
Frequency Range (Batt. Mode) | 50 Hz ± 0.1 Hz or 60Hz ± 0.1 Hz |
Current Crest Ratio | 3:1 |
Harmonic Distortion | ≦2% THD (Linear load)
≦3% THD (Non-linear load) |
EFFICIENCY & INDICATORS
AC Mode | 94% |
ECO Mode | 97% |
At Full Load | 91% |
Peak | 92% |
LCD | UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions |
CONNECTIVITY, CONTROL & MONITORING
Front panel | Status LED, Function keys, LCD display |
Communication | Smart RS232*
USB Port Emergency Power Off (EPO) |
BATTERY
Battery Voltage | ± 12V / 9 Ah |
Numbers | 16 ~ 20 pcs (adjustable) x 2 |
Typical Recharge Time | 9 hours recover to 90% capacity |
Charging Current | ± 4A |