Titan PPM Series (3P/3P)

Titan SERIES 400KVA

High Efficiency Online Double Conversion Technology

High Scalability

Unity Output Power Factor

Modular Design Lowers MTTR

N+1 and N+X Parallel Redundancy for power guarantee

Ease Of Installation and Maintenance

MODEL

Titan 30U-90-30HV 90KVA

GENERAL

UPS Type Tower
Phase 3 phase in / 3 phase out
Cabinet Capacity* 90KW
One Power Module Capacity 30KVA / 30KW
Max. Power Module Capacity 3
Max. Battery Set No.** 3
Dimension (mm) 1100 x 600 x 1475 (D x W x H)
Weight (kgs) 675

INPUT

Connection Type Terminal
Nominal Voltage 3 x 380VAC / 400VAC / 415VAC (3Ph+N)
Voltage Range 305 ~ 478 VAC at 100% load

208 ~ 304VAC at <70% load

Frequency Range 40Hz ~70Hz
Power Factor > 0.99 at 100% load

>0.98 at 50% load

THDi < 3% @ 100% load

OUTPUT

Connection Type Terminal
Nominal Voltage 3 x 380VAC / 400VAC / 415VAC (3Ph+N)
Voltage Regulation (Steady state) ≦ ± 1% Typical (balanced load)

≦ ± 2% Typical (unbalanced load)

Frequency Range (Synchronized) 46~54Hz or 56~64Hz
Overload Capability 1 hour for 110%

10 mins for 125%

1 min for 150% and 200ms for >150%

Efficiency Up to 94.5%
Harmonic Distortion ≦ 2% THD (Linear Load)

≦ 4% THD (Non-linear Load)

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

TYPE Built-in Battery
Nominal Voltage +/- 216V (12V x 36 Pcs)
Maximum Voltage +/- 240V (12V x 40 Pcs)
Minimum Voltage +/- 192V (12V x 32 Pcs)
Maximum Charging Current (Per Power Module) 8A
Titan 42U-120-30HV 120KVA

GENERAL

UPS Type Tower
Phase 3 phase in / 3 phase out
Cabinet Capacity* 120KW
One Power Module Capacity 30KVA / 30KW
Max. Power Module Capacity 4
Max. Battery Set No.** 5
Dimension (mm) 1100 x 600 x 2010 (D x W x H)
Weight (kgs) 932

INPUT

Connection Type Terminal
Nominal Voltage 3 x 380VAC / 400VAC / 415VAC (3Ph+N)
Voltage Range 305 ~ 478 VAC at 100% load

208 ~ 304VAC at <70% load

Frequency Range 40Hz ~70Hz
Power Factor > 0.99 at 100% load

>0.98 at 50% load

THDi < 3% @ 100% load

OUTPUT

Connection Type Terminal
Nominal Voltage 3 x 380VAC / 400VAC / 415VAC (3Ph+N)
Voltage Regulation (Steady state) ≦ ± 1% Typical (balanced load)

≦ ± 2% Typical (unbalanced load)

Frequency Range (Synchronized) 46~54Hz or 56~64Hz
Overload Capability 1 hour for 110%

10 mins for 125%

1 min for 150% and 200ms for >150%

Efficiency Up to 94.5%
Harmonic Distortion ≦ 2% THD (Linear Load)

≦ 4% THD (Non-linear Load)

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

TYPE Built-in Battery
Nominal Voltage +/- 216V (12V x 36 Pcs)
Maximum Voltage +/- 240V (12V x 40 Pcs)
Minimum Voltage +/- 192V (12V x 32 Pcs)
Maximum Charging Current (Per Power Module) 8A
Titan 30U-120-30HV Titan 30U-80-20HV 120KVA

GENERAL

UPS Type Tower
Phase 3 phase in / 3 phase out
Cabinet Capacity* 120 KW or 80 KW
One Power Module Capacity 30KVA / 30KW or 20KVA / 20KW
Max. Power Module Capacity 4
Max. Battery Set No.** -
Dimension (mm) 1100 x 600 x 1475 (D x W x H)
Weight (kgs) 335 or 333

INPUT

Connection Type Terminal
Nominal Voltage 3 x 380VAC / 400VAC / 415VAC (3Ph+N)
Voltage Range 305 ~ 478 VAC at 100% load

208 ~ 304VAC at <70% load

Frequency Range 40Hz ~70Hz
Power Factor > 0.99 at 100% load

>0.98 at 50% load

THDi < 3% @ 100% load

OUTPUT

Connection Type Terminal
Nominal Voltage 3 x 380VAC / 400VAC / 415VAC (3Ph+N)
Voltage Regulation (Steady state) ≦ ± 1% Typical (balanced load)

≦ ± 2% Typical (unbalanced load)

Frequency Range (Synchronized) 46~54Hz or 56~64Hz
Overload Capability 1 hour for 110%

10 mins for 125%

1 min for 150% and 200ms for >150%

Efficiency Up to 94.5%
Harmonic Distortion ≦ 2% THD (Linear Load)

≦ 4% THD (Non-linear Load)

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

TYPE Built-in Battery
Nominal Voltage +/- 216V (12V x 36 Pcs)
Maximum Voltage +/- 240V (12V x 40 Pcs)
Minimum Voltage +/- 192V (12V x 32 Pcs)
Maximum Charging Current (Per Power Module) 8A for 30KW power module

6A for 20KW power module

Titan 30U-180-30HV Titan 30U-120-20HV 180KVA

GENERAL

UPS Type Tower
Phase 3 phase in / 3 phase out
Cabinet Capacity* 180 KW or 120 KW
One Power Module Capacity 30KVA / 30KW or 20KVA / 20KW
Max. Power Module Capacity 6
Max. Battery Set No.** -
Dimension (mm) 1100 x 600 x 1475 (D x W x H)
Weight (kgs) 437.5 or 434.5

INPUT

Connection Type Terminal
Nominal Voltage 3 x 380VAC / 400VAC / 415VAC (3Ph+N)
Voltage Range 305 ~ 478 VAC at 100% load

208 ~ 304VAC at <70% load

Frequency Range 40Hz ~70Hz
Power Factor > 0.99 at 100% load

>0.98 at 50% load

THDi < 3% @ 100% load

OUTPUT

Connection Type Terminal
Nominal Voltage 3 x 380VAC / 400VAC / 415VAC (3Ph+N)
Voltage Regulation (Steady state) ≦ ± 1% Typical (balanced load)

≦ ± 2% Typical (unbalanced load)

Frequency Range (Synchronized) 46~54Hz or 56~64Hz
Overload Capability 1 hour for 110%

10 mins for 125%

1 min for 150% and 200ms for >150%

Efficiency Up to 94.5%
Harmonic Distortion ≦ 2% THD (Linear Load)

≦ 4% THD (Non-linear Load)

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

TYPE External Battery
Nominal Voltage +/- 216V (12V x 36 Pcs)
Maximum Voltage +/- 240V (12V x 40 Pcs)
Minimum Voltage +/- 192V (12V x 32 Pcs)
Maximum Charging Current (Per Power Module) 8A for 30KW power module

6A for 20KW power module

Titan 42U-200-20HV 200KVA

GENERAL

UPS Type Tower
Phase 3 phase in / 3 phase out
Cabinet Capacity* 200KW
One Power Module Capacity 20KW
Max. Power Module Capacity 10
Max. Battery Set No.** -
Dimension (mm) 1100 x 600 x 1475 (D x W x H)
Weight (kgs) 611

INPUT

Connection Type Terminal
Nominal Voltage 3 x 380VAC / 400VAC / 415VAC (3Ph+N)
Voltage Range 305 ~ 478 VAC at 100% load

208 ~ 304VAC at <70% load

Frequency Range 40Hz ~70Hz
Power Factor > 0.99 at 100% load

>0.98 at 50% load

THDi < 3% @ 100% load

OUTPUT

Connection Type Terminal
Nominal Voltage 3 x 380VAC / 400VAC / 415VAC (3Ph+N)
Voltage Regulation (Steady state) ≦ ± 1% Typical (balanced load)

≦ ± 2% Typical (unbalanced load)

Frequency Range (Synchronized) 46~54Hz or 56~64Hz
Overload Capability 1 hour for 110%

10 mins for 125%

1 min for 150% and 200ms for >150%

Efficiency Up to 94.5%
Harmonic Distortion ≦ 2% THD (Linear Load)

≦ 4% THD (Non-linear Load)

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

TYPE External Battery
Nominal Voltage +/- 216V (12V x 36 Pcs)
Maximum Voltage +/- 240V (12V x 40 Pcs)
Minimum Voltage +/- 192V (12V x 32 Pcs)
Maximum Charging Current (Per Power Module) 6A
Titan 42U-210-30HV 210KVA

GENERAL

UPS Type Tower
Phase 3 phase in / 3 phase out
Cabinet Capacity* 210KW
One Power Module Capacity 30KVA / 30KW
Max. Power Module Capacity 8
Max. Battery Set No.** -
Dimension (mm) 1100 x 600 x 2010 (D x W x H)
Weight (kgs) 549

INPUT

Connection Type Terminal
Nominal Voltage 3 x 380VAC / 400VAC / 415VAC (3Ph+N)
Voltage Range 305 ~ 478 VAC at 100% load

208 ~ 304VAC at <70% load

Frequency Range 40Hz ~70Hz
Power Factor > 0.99 at 100% load

>0.98 at 50% load

THDi < 3% @ 100% load

OUTPUT

Connection Type Terminal
Nominal Voltage 3 x 380VAC / 400VAC / 415VAC (3Ph+N)
Voltage Regulation (Steady state) ≦ ± 1% Typical (balanced load)

≦ ± 2% Typical (unbalanced load)

Frequency Range (Synchronized) 46~54Hz or 56~64Hz
Overload Capability 1 hour for 110%

10 mins for 125%

1 min for 150% and 200ms for >150%

Efficiency Up to 94.5%
Harmonic Distortion ≦ 2% THD (Linear Load)

≦ 4% THD (Non-linear Load)

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

TYPE External Battery
Nominal Voltage +/- 216V (12V x 36 Pcs)
Maximum Voltage +/- 240V (12V x 40 Pcs)
Minimum Voltage +/- 192V (12V x 32 Pcs)
Maximum Charging Current (Per Power Module) 8A
Titan 42U-300-30HV 300KVA

GENERAL

UPS Type Tower
Phase 3 phase in / 3 phase out
Cabinet Capacity* 300KW
One Power Module Capacity 30KVA / 30KW
Max. Power Module Capacity 10
Max. Battery Set No.** -
Dimension (mm) 1100 x 600 x 2010 (D x W x H)
Weight (kgs) 620

INPUT

Connection Type Terminal
Nominal Voltage 3 x 380VAC / 400VAC / 415VAC (3Ph+N)
Voltage Range 305 ~ 478 VAC at 100% load

208 ~ 304VAC at <70% load

Frequency Range 40Hz ~70Hz
Power Factor > 0.99 at 100% load

>0.98 at 50% load

THDi < 3% @ 100% load

OUTPUT

Connection Type Terminal
Nominal Voltage 3 x 380VAC / 400VAC / 415VAC (3Ph+N)
Voltage Regulation (Steady state) ≦ ± 1% Typical (balanced load)

≦ ± 2% Typical (unbalanced load)

Frequency Range (Synchronized) 46~54Hz or 56~64Hz
Overload Capability 1 hour for 110%

10 mins for 125%

1 min for 150% and 200ms for >150%

Efficiency Up to 94.5%
Harmonic Distortion ≦ 2% THD (Linear Load)

≦ 4% THD (Non-linear Load)

CONNECTIVITY, CONTROL & MONITORING

Front panel Status LED, Function keys, LCD display
Communication Smart RS232*

USB Port

Emergency Power Off (EPO)

BATTERY

TYPE External Battery
Nominal Voltage +/- 216V (12V x 36 Pcs)
Maximum Voltage +/- 240V (12V x 40 Pcs)
Minimum Voltage +/- 192V (12V x 32 Pcs)
Maximum Charging Current (Per Power Module) 8A

DOWNLOAD

Document Date Version
2017-08-07 1.00
2017-08-07 1.00

You may also like…

PRO63100-L-220 SERIES 10-120KVA

Extend SERIES 400KVA

PRO1000 RS/RL SERIES